580 9424200994 Rev N
Time Delay
Setting Range ........................................................... 0 to 60,000 ms
Accuracy.................................................................... ±1% or ±1 cycle, whichever is greater, plus trip time
for instantaneous response (0.0 setting)*
* Trip Time for 0.0 Delay Setting .............................. 1¼ cycles maximum for currents 5 times the pickup
setting. 1¾ cycles maximum for a current of 2
times pickup. Two cycles maximum for a current
of 1.05 times the pickup setting.
Automatic Setting Group Characteristics
Number of Setting Groups ........................................ 4
Control Modes
Automatic .................................................................. Cold-Load Pickup, Dynamic Load or Unbalance
External ..................................................................... Discrete Input Logic, Binary Input Logic
Switch Threshold
Range ........................................................................ 0.1 to 25 A (5 A), 0.02 to 5 A (1 A)
Accuracy.................................................................... ±2% or ±0.05 A (5 A), ±2% or ±0.01 A (1 A)
Switch Time
Range ........................................................................ 0 to 60 min with 1 min increments where 0 =
disabled
Accuracy.................................................................... ±0.5% or ±2 s, whichever is greater
BESTlogicPlus
Update Rate .............................................................. ¼ cycle
Specifications - 25 Hz Operation BE1-11g