Basler-electric BE1-11g Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Relais Basler-electric BE1-11g. Basler Electric BE1-11g User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 672
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
INSTRUCTION MANUAL
FOR
BE1-11g
Generator Protection System
Publication: 9424200994
Revision: N Sep-14
Vue de la page 0
1 2 3 4 5 6 ... 671 672

Résumé du contenu

Page 1 - INSTRUCTION MANUAL

INSTRUCTION MANUAL FOR BE1-11g Generator Protection System Publication: 9424200994 Revision: N Sep-14

Page 2

viii 9424200994 Rev N Auxiliary Voltage Input Verification - VX and VX 3rd (Fundamental and Third Harmonic) ... 369 Frequency Ver

Page 3

88 9424200994 Rev N be specified on the System Parameters, Sensing Transformers screen in BESTCOMSPlus. Refer to the Configuration chapter for more

Page 4

9424200994 Rev N 89 Table 29. Logic Inputs and Outputs Name Logic Function Purpose Block Input Disables the 50 function when true Trip Output True wh

Page 5

90 9424200994 Rev N Instantaneous Overcurrent (50) Protection BE1-11g

Page 6

9424200994 Rev N 91 Breaker Failure (50BF) Protection The breaker failure (50BF) element provides protection and security for the power system agains

Page 7

92 9424200994 Rev N Trip The Trip output becomes true if sensed current exceeds the Phase or Ground Pickup setting and the delay time expires in th

Page 8

9424200994 Rev N 93 Table 31. Logic Inputs and Outputs Name Logic Function Purpose Block Input Disables the 50BF function when true 50BFI Input Start

Page 9

94 9424200994 Rev N Breaker Failure (50BF) Protection BE1-11g

Page 10

9424200994 Rev N 95 Inverse Overcurrent (51) Protection Seven inverse overcurrent (51) elements monitor the current applied to the BE1-11g. An elemen

Page 11

96 9424200994 Rev N Unbalance Mode Unbalance mode provides unbalanced current protection. Two methods are available to calculate unbalanced current

Page 12

9424200994 Rev N 97 Parameter Description Explanation selected curve infinity if allowed to continue below pickup. Has greatest effect on curve shape

Page 13

9424200994 Rev N ix Unrestrained Functional Test Procedure ...

Page 14

98 9424200994 Rev N To use the 46 curve, the user should determine the K factor of the generator and the continuous (I2)2t rating of the generator

Page 15

9424200994 Rev N 99 𝐴𝑐𝑡𝑢𝑎𝑙 𝑃𝑖𝑐𝑘𝑢𝑝 𝐿𝑒𝑣𝑒𝑙 =𝑆𝑒𝑛𝑠𝑖𝑛𝑔 𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝐿𝑒𝑣𝑒𝑙𝑅𝑒𝑠𝑡𝑟𝑎𝑖𝑛𝑡 𝑃𝑖𝑐𝑘𝑢𝑝 𝑆𝑒𝑡𝑡𝑖𝑛𝑔× 51 𝑃ℎ𝑎𝑠𝑒 𝑃𝑖𝑐𝑘𝑢𝑝 𝑆𝑒𝑡𝑡𝑖𝑛𝑔 Equation 8. Restraint Pickup Level

Page 16

100 9424200994 Rev N When single-phase voltage sensing is used, only the inverse overcurrent element on the phase with voltage magnitude informatio

Page 17

9424200994 Rev N 101 Figure 65. Inverse Overcurrent Settings Screen Table 36. Operational Settings Setting Range Increment Unit of Measure Default

Page 18

102 9424200994 Rev N Setting Range Increment Unit of Measure Default C Coefficient 0 to 1 0.00001 C Coefficient 1.00000 N Coefficient 0.5 to 2.5

Page 19

9424200994 Rev N 103 Directional Overcurrent (67) Protection The 67 element provides directional supervision for the overcurrent tripping elements. T

Page 20

104 9424200994 Rev N The BE1-11g maintains memory voltage for 20 cycles to allow tripping for close in faults. When using memory voltage polarizati

Page 21

9424200994 Rev N 105 Table 37. Polarization Settings Setting Range/Purpose Default 67N Polarization Method IG Use Zero Sequence Current Polarization

Page 22

106 9424200994 Rev N Internal Constant Purpose Value Ground current (IG) Minimum Ground (IG) current threshold for Current Polarization test 0.50 A

Page 23

9424200994 Rev N 107 −=Relay2,Relay1,Relay0,Source2,Source1,Source0,Source2,Source1,Source0,Relay2,Rela

Page 24

x 9424200994 Rev N Specifications ...

Page 25

108 9424200994 Rev N Figure 67. Directional Overcurrent Relaying For more theory and mathematics of using sequence components for sensing directio

Page 26

9424200994 Rev N 109 Phase Current Differential (87) Protection The phase-current differential (87) element monitors the differential current and pro

Page 27

110 9424200994 Rev N Figure 68. 87 Phase Differential Protection Functional Block Diagram 0BPhase Current Differential (87) Protection BE1-11g

Page 28

9424200994 Rev N 111 Figure 69. Percentage Restrained Differential Characteristic Pickup and Trip The Pickup output occurs first, followed by the Tr

Page 29

112 9424200994 Rev N Harmonics The second and fifth harmonic functions check the ratio of the second and fifth harmonic operate current to the fund

Page 30

9424200994 Rev N 113 Figure 70. Phase Current Differential Element Logic Block Table 39. Logic Inputs and Outputs Name Function Purpose Block Input

Page 31

114 9424200994 Rev N If one of the calculated taps is outside the acceptable range (2 to 20 for 5 ampere units or 0.4 to 4 for 1 ampere units), the

Page 32

9424200994 Rev N 115 Figure 71. Phase Current Differential Settings Screen Figure 72. Phase Current Differential Operation Chart Table 41. Operati

Page 33

116 9424200994 Rev N Setting Range Increment Unit of Measure Default Flux Balance Pickup 0 or 0.1 to 5 0.01 amps 0 Time Delay 0 to 60,000 varies

Page 34

9424200994 Rev N 117 Neutral Current Differential (87N) Protection The neutral current differential (87N) element provides sensitive differential pro

Page 35

9424200994 Rev N 1 Introduction The BE1-11g Generator Protection System provides flexible, reliable, and economical protection, control, monitoring,

Page 36

118 9424200994 Rev N Pickup Calculations The differential value is calculated as shown in Equation 17 and Equation 18 and displayed in BESTCOMSPlus

Page 37

9424200994 Rev N 119 Figure 73. Current-Polarized Directional Scheme for BE1-11g CT Connection Logic Connections Neutral current differential elemen

Page 38

120 9424200994 Rev N Operational Settings Neutral current differential element operational settings are configured on the Neutral Current Different

Page 39

9424200994 Rev N 121 Phase Differential Protection: Self-Balancing and Split-Phase Configurations (50/51) The BE1-11g can be configured for the prote

Page 40

122 9424200994 Rev N Phase Differential Protection: Self-Balancing and Split-Phase Configurations (50/51) BE1-11g

Page 41

9424200994 Rev N 123 Power (32) Protection Two power (32) elements monitor three-phase real power (watts). An element can be configured to protect ag

Page 42

124 9424200994 Rev N Bus CT Configuration On protection systems equipped with two sets of CTs, the power element can monitor CT circuit 1 or CT cir

Page 43

9424200994 Rev N 125 Assuming polarity current and voltage connections as shown in Figure 76, forward power is defined as flowing into the Area EPS a

Page 44

126 9424200994 Rev N Logic Connections Power element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus. The power element logi

Page 45

9424200994 Rev N 127 Loss of Excitation - Reverse Var Based (40Q) Protection The loss of excitation - reverse var based (40Q) element monitors total

Page 46

2 9424200994 Rev N Features The BE1-11g protection system includes many features for the protection, monitoring, and control of power system equipm

Page 47

128 9424200994 Rev N Bus CT Configuration On protection systems equipped with two sets of CTs, the 40Q element can monitor CT circuit 1 or CT circu

Page 48

9424200994 Rev N 129 Operational Settings Loss of excitation - reverse var based element operational settings are configured on the Loss of Excitatio

Page 49

130 9424200994 Rev N Loss of Excitation - Reverse Var Based (40Q) Protection BE1-11g

Page 50

9424200994 Rev N 131 Distance (21) Protection Two distance (21) elements use the calculated impedance of a fault to determine the fault location. The

Page 51

132 9424200994 Rev N Trip The Trip output becomes true if a pickup condition exists for the duration of the element Time Delay. In BESTlogicPlus, t

Page 52

9424200994 Rev N 133 Figure 84. Distance Settings Screen Table 49. Operational Settings Setting Range Increment Unit of Measure Default Select Del

Page 53

134 9424200994 Rev N Distance (21) Protection BE1-11g

Page 54

9424200994 Rev N 135 Loss of Excitation - Impedance Based (40Z) Protection The loss of excitation - impedance based (40Z) element implements a two zo

Page 55

136 9424200994 Rev N If the pickup condition subsides before the element delay expires, the timer and Pickup output are reset, no corrective action

Page 56

9424200994 Rev N 137 Figure 85. Loss of Excitation - Impedance Based Element Logic Block Table 50. Logic Inputs and Outputs Name Logic Function Purp

Page 57

9424200994 Rev N 3 Clock The clock is used by the logging functions to timestamp events. BE1-11g timekeeping can be self-managed by the internal cloc

Page 58

138 9424200994 Rev N Table 51. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabled, Non-Voltage Control, Voltage C

Page 59

9424200994 Rev N 139 Out of Step (78OOS) Protection The Out of Step (78OOS) element detects out-of-step conditions by monitoring the rate of impedanc

Page 60

140 9424200994 Rev N Bus CT Configuration On protection systems equipped with two sets of CTs, the 78OOS element can monitor CT circuit 1 or CT cir

Page 61

9424200994 Rev N 141 Figure 89. Out of Step Element Logic Block Table 52. Logic Inputs and Outputs Name Logic Function Purpose Block Input Disables

Page 62

142 9424200994 Rev N Table 53. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabled or Enabled n/a n/a Disabled Rev

Page 63

9424200994 Rev N 143 Resistance Temperature Detector (49RTD) Protection Fourteen resistance temperature detector (49RTD) elements provide over/undert

Page 64

144 9424200994 Rev N annunciate the condition and to initiate corrective action. If a target is enabled for the element, the BE1-11g will record a

Page 65

9424200994 Rev N 145 Figure 92. Resistance Temperature Detector Settings Screen Table 55. Operational Settings Setting Range Increment Unit of Measu

Page 66

146 9424200994 Rev N Resistance Temperature Detector (49RTD) Protection BE1-11g

Page 67

9424200994 Rev N 147 Analog Input Protection Eight analog input elements monitor external analog input signals when two remote RTD modules are connec

Page 68

4 9424200994 Rev N BESTlogicPlus. A user-meaningful label can be assigned to each input and to each state (energized and de-energized) for use in r

Page 69

148 9424200994 Rev N Element Blocking The Block input provides logic-supervision control of the element. When true, the Block input disables the el

Page 70

9424200994 Rev N 149 Remote Analog Input Metering Analog input metering values are obtained through BESTCOMSPlus by using the Metering Explorer to op

Page 71

150 9424200994 Rev N Analog Input Protection BE1-11g

Page 72

9424200994 Rev N 151 Synchronizer (25A) The synchronizer (25A) element is available only in styles GxxxxxxxSxxxxx and GxxxxxJxTxxxxx of the BE1-11g a

Page 73

152 9424200994 Rev N Table 58. Common System and Sensing Transformer Combinations Phase VT Connection Phase Rotation Aux VT Connection Secondary Ph

Page 74

9424200994 Rev N 153 Frequency Correction Generator frequency correction is defined by the Slip Frequency setting and further refined by the Breaker

Page 75

154 9424200994 Rev N For the phase voltage input, if the connection is three-phase, 3W or 4W, all three phases are tested and must be above the liv

Page 76

9424200994 Rev N 155 • In Anticipatory mode: o Breaker Close Time setting must be set above zero (0) • In PLL mode: o Max Slip setting must be se

Page 77

156 9424200994 Rev N Figure 97. Synchronizer Element Logic Block Table 59. Logic Inputs and Outputs Name Logic Function Purpose Block Input Disab

Page 78

9424200994 Rev N 157 Name Logic Function Purpose Angle Synced Output When in PLL mode, true when the angle between the sources is less than the Break

Page 79

9424200994 Rev N 5 General Status Reporting The BE1-11g provides extensive general status reporting for monitoring, commissioning, and troubleshootin

Page 80

158 9424200994 Rev N Setting Range Increment Unit of Measure Default Voltage Source > Volt Dest Disabled or Enabled n/a n/a Disabled Freq S

Page 81

9424200994 Rev N 159 Virtual Control Switches (43) Five virtual control switch (43) elements provide manual control, locally and remotely, without us

Page 82

160 9424200994 Rev N 59N CUTOFF. The closed position of the switch may be labeled DISABLD and the open position may be labeled NORMAL. Control of V

Page 83

9424200994 Rev N 161 A Block Tag alarm indicates when a block tag is in place. Refer to the Alarms chapter for information on how to program alarms.

Page 84

162 9424200994 Rev N Figure 101. Virtual Control Switches Settings Screen Table 62. Operational Settings Setting Range Increment Unit of Measure D

Page 85

9424200994 Rev N 163 Logic Timers (62) Eight logic timer (62) elements emulate virtually any type of timer used in power system applications. The eig

Page 86

164 9424200994 Rev N Figure 103. One-Shot/Non-Retriggerable Mode One-Shot/Retriggerable Mode The one-shot retriggerable timer starts its timing se

Page 87

9424200994 Rev N 165 time delay for the output to change to false if it is presently true and the initiate input becomes false and stays false. In th

Page 88

166 9424200994 Rev N Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the Elements view, the default

Page 89

9424200994 Rev N 167 Table 64. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabled, Pickup/Dropout, One-Shot/Non-Retri

Page 90

6 9424200994 Rev N Vector Jump (78) Protection One vector jump protection element protects the generator by disconnecting it from the grid when a l

Page 91

168 9424200994 Rev N Logic Timers (62) BE1-11g

Page 92

9424200994 Rev N 169 Lockout Functions (86) Two lockout function (86) elements can be used to prevent operation of circuit breakers or other devices

Page 93

170 9424200994 Rev N Table 66. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabled or Enabled n/a n/a Disabled Retri

Page 94

9424200994 Rev N 171 Breaker Control Switch (101) The breaker control switch (101) element provides manual control of a circuit breaker or switch wit

Page 95

172 9424200994 Rev N 1. Use the Metering Explorer to open the Control/Breaker Control Switch tree branch (Figure 114). 2. Click on either the TRI

Page 96

9424200994 Rev N 173 Figure 115. Breaker Control Element Logic Block Table 67. Logic Inputs and Outputs Name Logic Function Purpose Trip Input Sets

Page 97

174 9424200994 Rev N Breaker Control Switch (101) BE1-11g

Page 98

9424200994 Rev N 175 Setting Groups Four setting groups allow for adapting the coordination settings to optimize them for a predictable situation. Se

Page 99

176 9424200994 Rev N Discrete Inputs When the setting group selection function block is enabled for Discrete Inputs, there is a direct correlation

Page 100 - Logic Connections

9424200994 Rev N 177 Figure 118. Input Control Binary Inputs CT Source The CT Source setting configures the setting group selection function to moni

Page 101 - Operational Settings

9424200994 Rev N 7 Power (32) Protection Two directional power elements are included in the BE1-11m and can be set for forward or reverse, overpower

Page 102

178 9424200994 Rev N to an alternate setting group that can accommodate the condition. The BE1-11g can be set to alarm for this condition using the

Page 103 - Element Operation

9424200994 Rev N 179 Figure 119. Setting Group Logic Block Table 70. Logic Inputs and Outputs Name Logic Function Purpose Automatic Input True when

Page 104

180 9424200994 Rev N Figure 120. Setting Group Setup Screen Table 71. Operational Settings Setting Range Purpose Default Mode Disabled Discrete In

Page 105

9424200994 Rev N 181 Setting Range Purpose Default Monitor Setting Disable, IP, IG, I2, 3I0, 60FL Determines when automatic setting group changes occ

Page 106

182 9424200994 Rev N Setting Groups BE1-11g

Page 107

9424200994 Rev N 183 Metering The BE1-11g measures the voltage and current inputs, displays those values in real time, records those values every qua

Page 108

184 9424200994 Rev N Table 72. Explanation of Figure 122 Call-Outs Call-Out Explanation A Holding the left mouse button down on a metering tab and

Page 109

9424200994 Rev N 185 Figure 123. Analog Metering, Voltage Screen Current - Primary and Secondary Metered current includes primary and secondary phas

Page 110 - Pickup and Trip

186 9424200994 Rev N Reactive Power Reactive power is metered over a range of −7,500 kilovars to +7,500 kilovars on five ampere nominal systems. On

Page 111 -

9424200994 Rev N 187 Figure 126. Analog Metering, Frequency Screen Synchronization Slip Frequency, Slip Angle, and Voltage Difference are metered. S

Page 113

8 9424200994 Rev N Breaker Control Switch (101) Tripping and closing of a selected breaker can be controlled by the virtual breaker control switch.

Page 114

188 9424200994 Rev N Figure 128. Analog Metering, Differential Screen Energy Energy is metered for positive and negative watthours and varhours. W

Page 115

9424200994 Rev N 189 Figure 129. Analog Metering, Energy Screen Click the Edit button to change the values. The Meter Energy Editor screen appears a

Page 116

190 9424200994 Rev N Figure 132. Analog Metering, Analog Outputs Screen RTD Meter Figure 133 illustrates the RTD Meter screen. Temperatures are di

Page 117

9424200994 Rev N 191 Sequence of Events A sequence of events recorder (SER) report is very useful in reconstructing the exact sequence and timing of

Page 118

192 9424200994 Rev N Figure 134. Sequence of Events Screen Viewing SER Data through the Web Page Interface Sequence of events summary can be viewe

Page 119

9424200994 Rev N 193 Fault Reporting The fault reporting function records and reports information about faults that have been detected by the BE1-11g

Page 120

194 9424200994 Rev N Table 75. Targets as Displayed Target Description 21-#-AB Distance, AB 21-#-BC Distance, BC 21-#-CA Distance, CA 24 Overexcita

Page 121

9424200994 Rev N 195 Target Description 59X-#-3V0 Auxiliary Overvoltage, 3V0-3ph VT 59X-#-V1 Auxiliary Overvoltage, Positive-Sequence 59X-#-V2 Auxili

Page 122

196 9424200994 Rev N Retrieving Target Information and Resetting Targets To view targets at the front-panel display, navigate to Metering > Stat

Page 123

9424200994 Rev N 197 BE1-11g protection systems have three identification fields: Device ID, Station ID, and User ID. These fields are used in the he

Page 124

9424200994 Rev N 9 Figure 1. Style Chart BE1-11g Introduction

Page 125

198 9424200994 Rev N Viewing and Downloading Fault Data through the Web Page Interface Fault report data can be viewed through the web page interfa

Page 126

9424200994 Rev N 199 o If the pickup or logic expressions stay true for more than 60 seconds, an alarm bit in the programmable alarm function is set

Page 127

200 9424200994 Rev N All channels are recorded (IA, IA Circuit 2, IB, IB Circuit 2, IC, IC Circuit 2, IG, IG Circuit 2, VA, VB, VC, VX, FP, FX, Ana

Page 128

9424200994 Rev N 201 Line Length describes the power line parameters for which distance is to be computed over. The parameters should be entered in u

Page 129

202 9424200994 Rev N Protective Fault Analysis Figure 142. Protective Fault Analysis Protective element picks upProtective element tripsBreaker a

Page 130

9424200994 Rev N 203 Table 78. Legend for Figure 142 Locator Description A A fault summary report and an oscillograph record are triggered when the P

Page 131

204 9424200994 Rev N Fault Reporting BE1-11g

Page 132

9424200994 Rev N 205 Alarms The BE1-11g monitors internal systems, external interfaces, and power system equipment and annunciates an alarm when one

Page 133

206 9424200994 Rev N Name Description Fuse Loss One or more phases of voltage lost I2 Demand Negative-sequence current unbalance demand IG Demand G

Page 134

9424200994 Rev N 207 Name Description S Demand Apparent power (VA) demand maximum exceeded Setting Change Setting change made by user Settings Group

Page 135

10 9424200994 Rev N Introduction BE1-11g

Page 136

208 9424200994 Rev N under Alarm Configuration. When active, the label of a user alarm is displayed on the Alarms screen on the front-panel display

Page 137

9424200994 Rev N 209 Reset will reset all logic alarms. Use the drag-and-drop method to connect a variable or series of variables to the Reset input.

Page 138

210 9424200994 Rev N Alarms BE1-11g

Page 139

9424200994 Rev N 211 Differential Reporting The BE1-11g records information about the phase current differential (87) status of the BE1-11g and creat

Page 140

212 9424200994 Rev N Differential Reporting BE1-11g

Page 141

9424200994 Rev N 213 Breaker Monitoring Breaker monitoring helps manage equipment inspection and maintenance expenses by providing extensive monitori

Page 142

214 9424200994 Rev N edit this value at the front-panel display. To view the breaker status using BESTCOMSPlus, use the Metering Explorer to open t

Page 143

9424200994 Rev N 215 Figure 150. Protective Fault Analysis Protective element picks upProtective element tripsBreaker auxiliary contact changes sta

Page 144

216 9424200994 Rev N Table 81. Legend for Figure 150 Locator Description A A fault summary report and an oscillograph record are triggered when the

Page 145

9424200994 Rev N 217 Figure 151. Breaker Monitoring Screen To connect the Block logic input, use the Settings Explorer within BESTCOMSPlus to open t

Page 146

9424200994 Rev N 11 Quick Start This chapter provides basic installation and setup information about the BE1-11g Generator Protection System. BE1-11g

Page 147

218 9424200994 Rev N be read or changed through the communication ports using BESTCOMSPlus. Use the Metering Explorer to open the Reports, Breaker

Page 148

9424200994 Rev N 219 Demands Demand recording promotes the ability of an electric power provider to plan for future upgrades. For example, increasing

Page 149

220 9424200994 Rev N Setting Range Increment Unit of Measure Default Phase Current Threshold 0 or 0.5 to 16 0.01 amps 0 Neutral/Ground Current Th

Page 150

9424200994 Rev N 221 Figure 155. Demand Current Screen Figure 156. Demand Power Screen Refer to the BESTnet™Plus chapter for information on viewing

Page 151

222 9424200994 Rev N Demands BE1-11g

Page 152

9424200994 Rev N 223 Load Profile The load profile recording function provides a running average of the demand and helps a customer determine when po

Page 153

224 9424200994 Rev N Load Profile BE1-11g

Page 154

9424200994 Rev N 225 Power Quality The BE1-11g offers class B power quality measurement performance as defined by IEC 610004-30. Power quality data c

Page 155

226 9424200994 Rev N Voltage Figure 159 illustrates the Power Quality, Voltage screen. Figure 159. Power Quality, Voltage Screen 10-Second Frequen

Page 156

9424200994 Rev N 227 Figure 161. Power Quality, Dip/Swell Screen Harmonics Figure 162 illustrates the Power Quality, Harmonic Voltage screen. The Ha

Page 157

12 9424200994 Rev N Table 1. System Recommendations for BESTCOMSPlus and the .NET Framework System Type Component Recommendation 32/64 bit Processo

Page 158

228 9424200994 Rev N Power Quality BE1-11g

Page 159

9424200994 Rev N 229 Trip Circuit Monitor (52TCM) A trip circuit monitor (52TCM) element continually monitors the circuit breaker trip circuit for vo

Page 160

230 9424200994 Rev N Figure 163. Trip Detector Circuit (J Type Case) Table 88. Current Draw for each Power Supply Voltage Rating (J Type Case) Pow

Page 161

9424200994 Rev N 231 Figure 164. Trip Detector Circuit (H or P Type Case) Table 89. Current Draw for each Power Supply Voltage Rating (H or P Type C

Page 162

232 9424200994 Rev N Figure 165 illustrates typical trip circuit monitor connections for the BE1-11g. Figure 165. Trip Circuit Voltage and Continu

Page 163

9424200994 Rev N 233 Figure 166. TCM with Other Devices Trip Circuit Monitor (52TCM) Enable/Disable Jumper (J Type Case) Note A BE1-11g in a J type

Page 164

234 9424200994 Rev N Figure 167. Trip Circuit Monitor Enable/Disable Jumper Location Logic Connections Trip circuit monitor logic connections are

Page 165

9424200994 Rev N 235 Operational Settings Trip circuit monitor element operational settings are configured on the Trip Circuit Monitor (52TCM) settin

Page 166

236 9424200994 Rev N Trip Circuit Monitor (52TCM) BE1-11g

Page 167

9424200994 Rev N 237 Fuse Loss (60FL) The fuse loss (60FL) element detects fuse loss or loss of potential in a three-phase system. Element logic conn

Page 168

9424200994 Rev N 13 Figure 2. Front Panel Label Example Connect rear terminals A6, A7, and A8 (ground) to a power supply. Figure 3 shows the rear te

Page 169

238 9424200994 Rev N Table 92. Fuse Loss Logic Parameters Input True Condition A Positive-sequence volts greater than 8.8% of the nominal voltage;

Page 170

9424200994 Rev N 239 Programmable Alarm The BE1-11g indicates an alarm condition when the 60FL element detects a fuse loss or loss of potential. The

Page 171

240 9424200994 Rev N Setting Purpose Block V2 Voltage Elements All functions that use the negative-sequence voltage (V2) measurement are blocked wh

Page 172

9424200994 Rev N 241 BESTnet™Plus BE1-11g Generator Protection Systems with an Ethernet port have a web page interface that can be used to view BE1-1

Page 173

242 9424200994 Rev N Figure 175. Real Time Data Page Demand Data Figure 176 illustrates the Demand Data page. Present and peak demand values are s

Page 174

9424200994 Rev N 243 Figure 176. Demand Data Page Faults Fault Summary Figure 177 illustrates the Fault Summary page. To view fault details and down

Page 175

244 9424200994 Rev N Figure 177. Fault Summary Page Fault Details Figure 178 illustrates the Fault Details page. Use the buttons to download oscil

Page 176

9424200994 Rev N 245 Sequence of Events Figure 179 illustrates the Sequence of Events Summary page. A summary of the sequence of events is shown on t

Page 177

246 9424200994 Rev N Figure 180. Power Quality Page BESTnet™Plus BE1-11g

Page 178

9424200994 Rev N 247 Mounting BE1-11g protection systems are available in two case configurations. J-option protection systems are supplied in a non-

Page 179

14 9424200994 Rev N Figure 4. PWR Rear Terminals (H or P Type Case) Start BESTCOMSPlus® and Activate BE1-11 Plugin To start BESTCOMSPlus, click th

Page 180

248 9424200994 Rev N Figure 182. J Type Case - Side Dimensions 7.91 [201.03]6.26 [159.08]1.03 [26.15]0.62 [15.62]0.41 [10.31]0.30 [7.68]8.41 [2

Page 181

9424200994 Rev N 249 Case cutout and drilling dimensions are shown in Figure 183. Figure 183. J Type Case - Cutout and Drilling Dimensions 3.03 (

Page 182

250 9424200994 Rev N An adapter plate to mount a J case in a GE S2 or ABB FT-21 cutout is shown in Figure 184. Order Basler part number 9108551021.

Page 183

9424200994 Rev N 251 An adapter plate to mount a J case in a ABB FT-31/FT-32 cutout is shown in Figure 185. Order Basler part number 9108551022. Fig

Page 184

252 9424200994 Rev N An adapter plate to mount a J case in a GE M1/M2 cutout or Basler M1 cutout is shown in Figure 186. Order Basler part number 9

Page 185

9424200994 Rev N 253 A J case retrofit mounting plate for the Multilin 489 consists of two parts. See Figure 187 and Figure 188. Order Basler part nu

Page 186

254 9424200994 Rev N Figure 188. Retrofit Mounting Plate (Basler P/N: 9424200073) – Part 2 Mounting BE1-11g

Page 187

9424200994 Rev N 255 A pivoting projection-mounting kit for a J case is shown in Figure 189. When installed, this kit provides rear access to connect

Page 188

256 9424200994 Rev N Figure 190. H1 Rack-Mount Case Dimensions Mounting BE1-11g

Page 189

9424200994 Rev N 257 Figure 191. H1 Panel-Mount Case Dimensions BE1-11g Mounting

Page 190

9424200994 Rev N 15 Figure 6. BESTCOMSPlus Splash Screen Figure 7. Communication Pull-Down Menu Figure 8. BE1-11 Connection Screen The BE1-11 plug

Page 191

258 9424200994 Rev N Adapter bracket 9289924100 allows a single BE1-11g to be mounted in a 19-inch rack (see Figure 192). A second adapter bracket

Page 192

9424200994 Rev N 259 If a single H1 BE1-11g (H style case) is to be rack mounted, the cutout and drilling dimensions of Figure 194 should be used. If

Page 193

260 9424200994 Rev N Mounting plate cutout and drilling dimensions for two dovetailed H1 protection systems are shown in Figure 196. Figure 196. D

Page 194

9424200994 Rev N 261 Part number 9289900016 is used to panel mount two dovetailed protection systems. Figure 197 gives the cutout and drilling dimens

Page 195

262 9424200994 Rev N Dovetailing Procedure Basler H1 cases can be interlocked by means of a tenon and mortise on the left and right sides of each c

Page 196

9424200994 Rev N 263 Figure 198. Dovetailing Procedure BE1-11g Mounting

Page 197

264 9424200994 Rev N Mounting BE1-11g

Page 198

9424200994 Rev N 265 Terminals and Connectors Connections to the BE1-11g are dependent on the application and logic scheme selected by the user. As a

Page 199

266 9424200994 Rev N Figure 200. Rear-Panel Connections with Fiber Optic Ethernet (J Type Case) Terminal Blocks J-style cases use two sizes of ter

Page 200

9424200994 Rev N 267 Figure 201. Rear-Panel Connections with RJ45 Ethernet (H or P Type Case) Figure 202. Rear-Panel Connections with Fiber Optic E

Page 201

16 9424200994 Rev N Programming the BE1-11g This section contains an introduction to BESTCOMSPlus, explains summary screens, and gives an example o

Page 202

268 9424200994 Rev N By ANSI convention, current transformer polarity will face away from the protected winding of a transformer, motor, generator,

Page 203

9424200994 Rev N 269 Figure 205. Example of Reversed CT Polarity BE1-11g Terminals and Connectors

Page 204

270 9424200994 Rev N Terminals and Connectors BE1-11g

Page 205

9424200994 Rev N 271 Typical Connections Typical external dc connections for the BE1-11g are shown in Figure 206. Figure 206. Typical External DC C

Page 206

272 9424200994 Rev N Typical external ac connections (generator differential) for the BE1-11g are shown in Figure 207. Figure 207. Typical AC Conn

Page 207

9424200994 Rev N 273 Typical external ac connections (overall differential) for the BE1-11g are shown in Figure 208. Figure 208. Typical AC Connecti

Page 208

274 9424200994 Rev N Three-phase voltage sensing, alternate VT inputs are shown in Figure 209. Figure 209. Three-Phase Voltage Sensing, Alternate

Page 209

9424200994 Rev N 275 Single-phase current sensing connections are shown in Figure 210. Figure 210. Single-Phase Current Sensing Connections Note So

Page 210

276 9424200994 Rev N Typical Connections BE1-11g

Page 211

9424200994 Rev N 277 Power System Applications The following figures show examples of the applications that can be served by the Basler Electric BE1-

Page 212

9424200994 Rev N 17 Figure 10. View Drop-Down Button Summary Screens Summary screens provide an overview of the system setup. The legend, located in

Page 213

278 9424200994 Rev N Figure 212. One-Line Diagram of High Impedance Grounded Generator Protection with Sequential Trip Power System Applicat

Page 214

9424200994 Rev N 279 Figure 213. One-Line Diagram of Low Impedance Grounded Generator Protection with Sequential Trip BE1-11g Power System Ap

Page 215

280 9424200994 Rev N Figure 214. One-Line Diagram of Basic High Impedance Grounded Generator Protection Power System Applications BE1-11g

Page 216

9424200994 Rev N 281 Figure 215. One-Line Diagram of Basic Low Impedance Grounded Generator Protection BE1-11g Power System Applications

Page 217

282 9424200994 Rev N Figure 216. One-Line Diagram of High Impedance Grounded Generator Protection with Differential and Sequential Trip Power S

Page 218

9424200994 Rev N 283 BESTCOMSPlus® Software BESTCOMSPlus is a Windows®-based, PC application that provides a user-friendly, graphical user interface

Page 219

284 9424200994 Rev N Installation BESTCOMSPlus software is built on the Microsoft® .NET Framework. The setup utility that installs BESTCOMSPlus on

Page 220

9424200994 Rev N 285 Connect a USB Cable The USB driver was copied to your PC during BESTCOMSPlus installation and is installed automatically after p

Page 221

286 9424200994 Rev N Figure 220. Communication Pull-Down Menu The BE1-11 Connection screen shown in Figure 221 appears. Select USB Connection and

Page 222

9424200994 Rev N 287 Figure 222. Device Plugin Requires Activation The Activate Device Plugin pop-up appears. Refer to Figure 223. Figure 223. Acti

Page 223

9424200994 Rev N i Preface This instruction manual provides information about the installation and operation of the BE1-11g Generator Protection Syst

Page 224

18 9424200994 Rev N Programming Example Changing default logic is sometimes required to match the protection requirements of the system. Additional

Page 225

288 9424200994 Rev N Figure 224. Activation Key Email The Get Data button extracts the Device, Email Address, and Activation Key from the Windows

Page 226

9424200994 Rev N 289 Figure 226. Processing, Please Wait… Advanced Properties Click the Advanced button on the Connection screen to display the Adva

Page 227

290 9424200994 Rev N Menu Item Description Export To File Save settings as a *.csv file Print Print, export, or send a settings file Properties Vie

Page 228

9424200994 Rev N 291 Menu Item Description About View general, detailed build, and system information Lower Menu Bar (BE1-11 Plugin) Lower menu bar

Page 229

292 9424200994 Rev N • Protection • Control • BESTlogicPlus Programmable Logic Logic setup will be necessary after making certain setting change

Page 230

9424200994 Rev N 293 Figure 228. Processing, Please Wait… Printing a Settings File To view a preview of the settings printout, select Print Preview

Page 231

294 9424200994 Rev N Figure 230. BESTCOMSPlus Settings Compare Auto Export Metering The auto export metering function automatically exports meteri

Page 232

9424200994 Rev N 295 BESTCOMSPlus® Updates Ongoing BE1-11g functionality enhancements may make future BE1-11g firmware updates desirable. Enhancement

Page 233

296 9424200994 Rev N BESTCOMSPlus® Software BE1-11g

Page 234

9424200994 Rev N 297 BESTlogic™Plus BESTlogicPlus Programmable Logic is a programming method used for managing the input, output, protection, control

Page 235

9424200994 Rev N 19 becomes an Off-Page Input. The Trip Bus Off-Page Input in connected to physical Output 1 on the BE1-11g. Therefore, the OUT1 cont

Page 236

298 9424200994 Rev N BESTlogic™Plus Composition There are three main groups of objects used for programming BESTlogicPlus. These groups are I/O, Co

Page 237

9424200994 Rev N 299 Name Description Symbol Relay Trouble Alarm True when a Relay Trouble alarm is active. Refer to the Alarms chapter for more info

Page 238

300 9424200994 Rev N Name Description Symbol Pickup and Dropout Timers Pick Up Timer A pickup timer produces a true output when the elapsed time is

Page 239

9424200994 Rev N 301 Elements This group contains elements for the 21, 24, 25, 25A, 27P, 27X, 32, 40Q, 40Z, 43, 49RTD, 50, 50BF, 51, 59P, 59X, 60FL,

Page 240

302 9424200994 Rev N Name Description Symbol 32-x Power Protection. Refer to the Power (32) Protection chapter. 40Q Loss of Excitation - Reverse V

Page 241

9424200994 Rev N 303 Name Description Symbol 51-x Inverse Overcurrent Protection. Refer to the Inverse Overcurrent (51) Protection chapter. 59P-x Ph

Page 242

304 9424200994 Rev N Name Description Symbol 87 Current Differential Protection. Refer to the Current Differential (87) Protection chapter. 87N-1

Page 243

9424200994 Rev N 305 Name Description Symbol 43-x Virtual Control Switches. Refer to the Virtual Control Switches (43) chapter. 62-x Logic Timers. R

Page 244

306 9424200994 Rev N Name Description Symbol Reporting and Alarms 52TCM Trip Circuit Monitor. Refer to the Trip Circuit Monitor (52TCM) chapter. 6

Page 245

9424200994 Rev N 307 Name Description Symbol MAJORALMRST Major Alarm Reset. Refer to the Alarms chapter. MINORALMRST Minor Alarm Reset. Refer to the

Page 246

20 9424200994 Rev N Figure 15. BESTlogicPlus Logic Page 2 Figure 16. BESTlogicPlus Logic Page 3 Step 10: In this step, the Pickup output of the 5

Page 247

308 9424200994 Rev N Caution Always remove the BE1-11g from service prior to changing or modifying the active logic scheme. Attempting to modify a

Page 248

9424200994 Rev N 309 Table 101. Default Function Block Logic Function Purpose BESTlogic™Plus Inputs 50-1 Used for instantaneous phase overcurrent pr

Page 249

310 9424200994 Rev N Figure 233. One-Line Drawing for Default Logic BESTlogic™Plus BE1-11g

Page 250

9424200994 Rev N 311 Figure 234. Logic Diagram for Default Logic Copying and Renaming Preprogrammed Logic Schemes Copying a saved logic scheme to th

Page 251

312 9424200994 Rev N Programming BESTlogic™Plus BESTCOMSPlus is used to program BESTlogicPlus. Using BESTCOMSPlus is analogous to physically attach

Page 252

9424200994 Rev N 313 Figure 235. Pickup and Dropout Timer Logic Blocks Offline Logic Simulator The offline logic simulator allows you to change the

Page 253

314 9424200994 Rev N files. Refer to Figure 237. For information on Settings Files management, refer the BESTCOMSPlus Software chapter. Figure 237

Page 254

9424200994 Rev N 315 A Page Setup icon is also provided on the BESTlogicPlus Programmable Logic toolbar allowing you to select Paper Size, Paper Sour

Page 255

316 9424200994 Rev N BESTlogic™Plus BE1-11g

Page 256

9424200994 Rev N 317 Communication This chapter describes the connections and settings for BE1-11g communication. In addition to standard USB, RS-485

Page 257

9424200994 Rev N 21 Figure 17. BESTlogicPlus Programming OUT4 Step 11: In this step, the Pickup output of the 50-3 element is connected to User Alar

Page 258

318 9424200994 Rev N Figure 240. RS-485 DB-37 to BE1-11g Ethernet Setup Located on the rear panel, the optional Ethernet communication port provid

Page 259

9424200994 Rev N 319 5. Select Configure, Ethernet from the Communication pull-down menu. If the BE1-11g is connected properly, the Configure Ethern

Page 260

320 9424200994 Rev N Note The PC running BESTCOMSPlus software must be configured correctly to communicate with the BE1-11g. The PC must have an IP

Page 261

9424200994 Rev N 321 244. Use the drag-and-drop method to connect a variable or series of variables to the input. Refer to the BESTlogicPlus chapter

Page 262

322 9424200994 Rev N Figure 246. DNP Settings, Miscellaneous Settings Screen Unsolicited Response Support The Unsolicited Response Support screen

Page 263

9424200994 Rev N 323 Figure 248. Default Variations Screen DNP Analog Points Mapping Analog points can be mapped to any of the available analog user

Page 264

324 9424200994 Rev N To map a Binary Point to the Binary User Map: 1. Select a binary point in the left-hand column. 2. Click on the Add >>

Page 265

9424200994 Rev N 325 Modbus™ Setup Settings for Modbus are made by using the Settings Explorer to open the Communications, Modbus tree branch. Settin

Page 266

326 9424200994 Rev N Figure 253. Modbus Mapping Screen Communication BE1-11g

Page 267

9424200994 Rev N 327 Security Multiple levels of BE1-11g security give personnel the level of access appropriate for the tasks they routinely perform

Page 268

22 9424200994 Rev N Figure 19. BESTlogicPlus Toolbar Step 13: In the Settings Explorer, expand Programmable Outputs, Contact Outputs, and name Out

Page 269

328 9424200994 Rev N 2. Enter the username and password of the administrator and then click the Log In button. The default Administrator username

Page 270

9424200994 Rev N 329 2. The Login dialog box pops up. See Figure 254. An administrator access level is required to set up port access. Enter the use

Page 271

330 9424200994 Rev N Table 108. Settings for Access Control Setting Range Increment Unit Default Access Timeout Delay 10 to 3,600 1 seconds 300 Log

Page 272

9424200994 Rev N 331 Timekeeping The BE1-11g provides a real-time clock with capacitor backup that is capable of operating the clock for up to 24 hou

Page 273

332 9424200994 Rev N Figure 259. Clock Setup Screen Table 109. Settings for Clock Setting Range Increment Unit Default Time Zone Hour Offset –12 t

Page 274

9424200994 Rev N 333 Figure 260. Status, Real Time Clock Screen IRIG Port IRIG time code signal connections are located on the rear panel. When a va

Page 275

334 9424200994 Rev N Backup Battery for the Real-Time Clock The backup battery for the real time clock is a standard feature of the BE1-11g. A batt

Page 276

9424200994 Rev N 335 Figure 261. Front-Panel Circuit Board, Backup Battery Location BE1-11g Timekeeping

Page 277

336 9424200994 Rev N Figure 262. Re-Attaching the Front Cover Battery Replacement Procedure for H or P Style Case Battery access is located on the

Page 278

9424200994 Rev N 337 Figure 263. Digital Circuit Board, Backup Battery Location Backup Battery(+) Side UpFrontBE1-11g Timekeeping

Page 279

9424200994 Rev N 23 Figure 21. User Programmable Alarms Screen Figure 22. OUT4 and USERALM1 with User-Defined Labels BE1-11g Quick Start

Page 280

338 9424200994 Rev N Timekeeping BE1-11g

Page 281

9424200994 Rev N 339 Device Information BE1-11g identification labels, firmware version, serial number, and style number are found on the Device Info

Page 282

340 9424200994 Rev N Device Info Information about a BE1-11g communicating with BESTCOMSPlus can be obtained on the Device Info screen of BESTCOMSP

Page 283

9424200994 Rev N 341 screen in BESTCOMSPlus. The Basler Electric Device Package Uploader screen will appear. See Figure 266. Figure 266. Basler Elec

Page 284

342 9424200994 Rev N Device Information BE1-11g

Page 285

9424200994 Rev N 343 Configuration BE1-11g inputs consist of three-phase current inputs and ground, three-phase voltage inputs, and one auxiliary vol

Page 286

344 9424200994 Rev N VT Connections When four-wire VT connections are used, the BE1-11g measures the three-phase to neutral voltages and calculates

Page 287

9424200994 Rev N 345 CBA3VarsVarsVarsVars ++=φ where: XPNPIV ∠−∠=φ For Sensing Type: Three-wire In three-wire sensing mode, the equivalent LN v

Page 288

346 9424200994 Rev N Power System Settings The BE1-11g requires information about the power system to provide metering, fault reporting, fault loca

Page 289

9424200994 Rev N 347 Settings Power system settings are configured on the Power System settings screen (Figure 268) in BESTCOMSPlus. Setting ranges a

Page 290

24 9424200994 Rev N Quick Start BE1-11g

Page 291

348 9424200994 Rev N BESTCOMSPlus Navigation Path: Settings Explorer, System Parameters, Sensing Transformers HMI Navigation Path: Settings Explore

Page 292

9424200994 Rev N 349 Settings Sensing transformers settings are configured on the Sensing Transformers settings screen (Figure 269) in BESTCOMSPlus.

Page 293

350 9424200994 Rev N BESTCOMSPlus Navigation Path: Settings Explorer, System Parameters, Transformer Setup HMI Navigation Path: Settings Explorer,

Page 294

9424200994 Rev N 351 Determining the Transformer Connection Parameters Wye and Autotransformer Windings. The transformer connection for a CT input ci

Page 295

352 9424200994 Rev N compensate for the ±30°, ±60°, ±90°, ±120°, ±150°, and ±180° phase shifts that are possible in transformers and sensing CT con

Page 296

9424200994 Rev N 353 Table 115. CT Input Circuit Settings for Non-transformer or Wye-only Application Transformer Connection CT Input Connection BE1-

Page 297

354 9424200994 Rev N Transformer Connection CT Input Connection BE1-11g Settings Compensation Applied TX CT Phase Rotation ZAC WYE ZAC WYE W

Page 298

9424200994 Rev N 355 Table 118. CT Input Circuit Settings 3 for Delta/Wye Circuit Applications Transformer Connection CT Input Connection BE1-11g Set

Page 299

356 9424200994 Rev N Transformer Connection CT Input Connection BE1-11g Settings Compensation Applied TX CT Phase Rotation DAC DAC DAC DAC W

Page 300

9424200994 Rev N 357 Note The CT input circuit settings are used by the auto-tap calculation function to calculate the correct tap adjustment factor

Page 301

9424200994 Rev N 25 Controls and Indicators BE1-11g controls and indicators are located on the front panel and include sealed membrane switches, LED

Page 302

358 9424200994 Rev N Table 119. Internal Compensation Chart IEC Transformer Setup The IEC setup table is aimed at describing transformers that us

Page 303

9424200994 Rev N 359 Figure 274. IEC Transformer Setup Screen Display Units The Display Units screen is shown in Figure 275. System Units This setti

Page 304

360 9424200994 Rev N Configuration BE1-11g

Page 305

9424200994 Rev N 361 Introduction to Testing The need to test protection systems to confirm performance as designed by manufacturers has always exist

Page 306

362 9424200994 Rev N • Setting validation • Proper operation of equipment (main or auxiliary) • Proper alarming (to SCADA) and/or targeting Peri

Page 307

9424200994 Rev N 363 BE1-11g Self-Test All internal circuitry and software that affect the BE1-11g core functionality are monitored by the continuous

Page 308

364 9424200994 Rev N Introduction to Testing BE1-11g

Page 309

9424200994 Rev N 365 Acceptance Testing Although Basler Electric performs detailed acceptance testing on all new protection systems, it is generally

Page 310

366 9424200994 Rev N IRIG Verification (if used) Purpose: To verify that the BE1-11g acquires and updates IRIG time and date information. Step 1:

Page 311

9424200994 Rev N 367 Step 7: Use the Metering Explorer in BESTCOMSPlus to return to the Control, Output Override screen and click on the Enabled b

Page 312

26 9424200994 Rev N Table 2. Front Panel Descriptions (J Type Case) Locator Description A Power Indicator – This green LED lights when operating po

Page 313

368 9424200994 Rev N current measurements can also be verified on the Metering > Analog Metering > Current > Current Circuit 2 > Second

Page 314

9424200994 Rev N 369 Table 123. Voltage Circuit Verification Values Applied Voltage Measured Voltage Lower Limit Upper Limit 80 volts 79.6 V 80.4 V 1

Page 315

370 9424200994 Rev N Step 2: Apply the voltage values listed in Table 124 and verify voltage-measuring accuracy by using the Metering Explorer i

Page 316

9424200994 Rev N 371 Commissioning Testing Special precautions should be taken to ensure that all tests are performed with safety as the greatest con

Page 317

372 9424200994 Rev N Verify that the selected output has changed state on the Control, Output Override screen of BESTCOMSPlus or the front-panel di

Page 318

9424200994 Rev N 373 Protection and Control Function Verification Before placing the BE1-11g in service, the user should ensure that all system ac an

Page 319

374 9424200994 Rev N Energy Data and Demand BESTCOMSPlus Navigation Path: Metering Explorer, Demand HMI Navigation Path: Metering Explorer, Demand

Page 320

9424200994 Rev N 375 Fault Summary Reports BESTCOMSPlus Navigation Path: Metering Explorer, Reports, Fault Records HMI Navigation Path: Metering Expl

Page 321

376 9424200994 Rev N Commissioning Testing BE1-11g

Page 322

9424200994 Rev N 377 Periodic Testing Because the BE1-11g has extensive internal test capabilities, periodic testing of the protection system can be

Page 323

9424200994 Rev N 27 Figure 24. Front Panel (H or P Type Case) Table 3. Front Panel Descriptions (H or P Type Case) Locator Description A Display – 6

Page 324

378 9424200994 Rev N Note If verifying the analog measurement circuits by comparison to independent devices is used, you should ensure that the two

Page 325

9424200994 Rev N 379 Overexcitation (24) Test Functional testing is a way to assess this protection system’s suitability for your application. Functi

Page 326

380 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Element Mode Enabled Protection, Voltage, Overexcitation Enables 24 function 24

Page 327

9424200994 Rev N 381 Step 10: (Optional.) Repeat steps 1 through 9 for the B-phase and C-phase voltage inputs. Step 11: (Optional.) Repeat steps 1

Page 328

382 9424200994 Rev N Step 3: All inverse timing tests are based on % of nominal Volts/Hertz (1 PU value). Refer to the Time Curve Characteristic

Page 329

9424200994 Rev N 383 Table 131. Definite Time Verification Test Settings Setting Value Description Inverse Time Pickup 0 Disables Inverse Time Pickup

Page 330

384 9424200994 Rev N Step Pickup Setting Low Actual Pickup High Low* Actual Dropout High* Pass/Fail 15 2.36 2.31 V/Hz 2.41 V/Hz 2.289 V/Hz 2.336

Page 331

9424200994 Rev N 385 Sync-Check (25) Test Functional testing is a way to assess this protection system’s suitability for your application. Functional

Page 332

386 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure 277. • Blocking is disabled. •

Page 333

9424200994 Rev N 387 Step 10: Increase the voltage until OUT2 closes (90 volts). Record the result. Step 11: (Optional.) Repeat steps 3 through 10

Page 334

ii 9424200994 Rev N 12570 State Route 143 Highland IL 62249-1074 USA www.basler.com [email protected] Tel: +1 618.654.2341 Fax: +1 618.654.2351

Page 335

28 9424200994 Rev N Locator Description J Edit Pushbutton – Settings changes are made at the front panel using this pushbutton. When pushed, this s

Page 336

388 9424200994 Rev N Table 135. Inverse Time and Definite Time Pickup Test Settings (25) Setting Value Description Voltage Difference 10% Sets volt

Page 337

9424200994 Rev N 389 Step Dropout Delay Setting Low Actual Timing High Pass/Fail 6 VTP - Dead V Dropout Delay - 5000 ms 4,968 ms 5,032 ms P / F

Page 338

390 9424200994 Rev N Sync-Check (25) Test BE1-11g

Page 339

9424200994 Rev N 391 Phase Undervoltage (27P) Test Functional testing is a way to assess this protection system’s suitability for your application. F

Page 340

392 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 279. • Blocking is disabled. •

Page 341

9424200994 Rev N 393 Step 2: Prepare to monitor the 27P-1 timings. Timing accuracy is verified by measuring the elapsed time between a sensing volta

Page 342

394 9424200994 Rev N Phase Undervoltage (27P) Test BE1-11g

Page 343

9424200994 Rev N 395 Auxiliary Undervoltage (27X) Test Functional testing is a way to assess this protection system’s suitability for your applicatio

Page 344

396 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Timing Mode Definite Protection, Voltage, Undervoltage (27X-1) Selects definite

Page 345

9424200994 Rev N 397 Table 141. Timing Test Settings (3V0 Mode) Pickup Setting Time Delay 65 V 2,000 ms 65 V 5,000 ms 65 V 10,000 ms Step 2: Prepare

Page 346

9424200994 Rev N 29 1. Press the Edit pushbutton. 2. Enter the username by pressing the UP or DOWN scrolling pushbuttons until the proper first cha

Page 347

398 9424200994 Rev N Figure 281. BESTlogicPlus Settings (V1 Mode) Table 143. Pickup Test Settings (V1 Mode) Pickup Setting Time Delay 78 V 50 ms 3

Page 348

9424200994 Rev N 399 Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 144. Record the results. Step 6: (Optional.)

Page 349

400 9424200994 Rev N Step 4: Prepare to monitor the 27X-1 function operation. Operation can be verified by monitoring OUT2 (see Figure 282). Step

Page 350

9424200994 Rev N 401 Setting Value BESTCOMSPlus Screen Description Inhibit Level 10 V Protection, Voltage, Undervoltage (27X-1) Sets inhibit level to

Page 351

402 9424200994 Rev N Table 150. Timing Test Settings (Vx Fundamental Mode) Pickup Setting Time Delay 115 V 2,000 ms 115 V 5,000 ms 115 V 10,000 ms

Page 352

9424200994 Rev N 403 Figure 284. BESTlogicPlus Settings (Vx Third Harmonic Mode) Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Underv

Page 353

404 9424200994 Rev N Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 153. Record the results. Step 6: (Optional

Page 354

9424200994 Rev N 405 Timing Verification (V1 Mode) Time Delay Range = 50 to 600,000 ms Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater Ste

Page 355

406 9424200994 Rev N Timing Verification (Vx Fundamental Mode) Time Delay Range = 50 to 600,000 ms Timing Accuracy = ±0.5% or ±2 cycles, whichever

Page 356

9424200994 Rev N 407 Phase Overvoltage (59P) Test Functional testing is a way to assess this protection system’s suitability for your application. Fu

Page 357

30 9424200994 Rev N To operate the switch, use the following procedure: 1. Use the scrolling pushbuttons to scroll to Metering, Control, Virtual S

Page 358

408 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 285. • Blocking is disabled. •

Page 359

9424200994 Rev N 409 Step 2: Prepare to monitor the 59P-1 timings. Timing accuracy is verified by measuring the elapsed time between a sensing volta

Page 360

410 9424200994 Rev N Phase Overvoltage (59P) Test BE1-11g

Page 361

9424200994 Rev N 411 Auxiliary Overvoltage (59X) Test Functional testing is a way to assess this protection system’s suitability for your application

Page 362

412 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 286. • Blocking is disabled. •

Page 363

9424200994 Rev N 413 Step 2: Prepare to monitor the 59X-1 timings. Timing accuracy is verified by measuring the elapsed time between a sensing volta

Page 364

414 9424200994 Rev N Table 161. Pickup Test Settings (V1 Mode) Pickup Setting Time Delay 82 V 50 ms 42 V 50 ms 25 V 50 ms Step 4: Prepare to monit

Page 365

9424200994 Rev N 415 Table 163. Operational Settings (V2 Mode) Setting Value BESTCOMSPlus Screen Description Phase VT Ratio 1 System Parameters, Sens

Page 366

416 9424200994 Rev N Step 7: Verify the pickup and dropout accuracy at 120 Vac for a pickup setting of 42 V (126 Vac on test set) and 70 Vac for a

Page 367

9424200994 Rev N 417 Figure 289. BESTlogicPlus Settings (Vx Fundamental Mode) Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Overvolta

Page 368

9424200994 Rev N 31 Figure 26. Front-Panel Display Setup Screen Table 4. Settings for Front-Panel Display Locator Setting Range Increment Unit Defau

Page 369

418 9424200994 Rev N Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 168. Record the results. Step 6: (Optional

Page 370

9424200994 Rev N 419 Step 5: Connect and apply a single-phase, 120 Vac, 3rd harmonic voltage source to the Vx input, terminals C17 (polarity) and C1

Page 371

420 9424200994 Rev N Timing Verification (3V0 Mode) Time Delay Range = 50 to 600,000 ms Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater

Page 372

9424200994 Rev N 421 Step Time Delay Setting Low Actual Timing High Pass/Fail 4 2,000 ms 1,968 ms 2,032 ms P / F 5 5,000 ms 4,968 ms 5,032 ms P

Page 373

422 9424200994 Rev N Auxiliary Overvoltage (59X) Test BE1-11g

Page 374

9424200994 Rev N 423 Vector Jump (78V) Test Functional testing is a way to assess this protection system’s suitability for your application. Function

Page 375

424 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 291. • Blocking is disabled. •

Page 376

9424200994 Rev N 425 Timing Verification Timing Accuracy = 150 ms or less Step Time Delay Actual Timing Pass/Fail 6 150 ms P / F 7 150 ms P /

Page 377

426 9424200994 Rev N Vector Jump (78V) Test BE1-11g

Page 378

9424200994 Rev N 427 Frequency (81) Test Functional testing is a way to assess this protection system’s suitability for your application. Functional

Page 379

32 9424200994 Rev N Controls and Indicators BE1-11g

Page 380

428 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 292. • Blocking is disabled. •

Page 381

9424200994 Rev N 429 Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 293. • Blocking is disabled. • O

Page 382

430 9424200994 Rev N Step 2: Prepare to monitor the 81-1 timings. Timing accuracy is verified by measuring the elapsed time between a frequency

Page 383

9424200994 Rev N 431 Step 3: Prepare to monitor the 81-1 function operation. Operation can be verified by monitoring OUT2 (see Figure 294). Step 4

Page 384

432 9424200994 Rev N • Blocking is disabled. • OUT1 closes for 81-1 Trip. • OUT2 closes for 81-1 Pickup. • Fault recording is enabled. Figure

Page 385

9424200994 Rev N 433 Underfrequency Pickup Verification Pickup Setting Range = 15 to 70 Hz Pickup Accuracy = ±0.01 Hz Reset = 0.02 Hz ±0.01 Hz of the

Page 386

434 9424200994 Rev N Frequency (81) Test BE1-11g

Page 387

9424200994 Rev N 435 Instantaneous Overcurrent (50) Test Functional testing is a way to assess this protection system’s suitability for your applicat

Page 388

436 9424200994 Rev N Figure 296. BESTlogicPlus Settings (Phase Mode) Step 3: Use BESTCOMSPlus to open the Protection, Current, Instantaneous Ov

Page 389

9424200994 Rev N 437 Table 183. Timing Test Settings (Phase Mode) Pickup Setting Time Delay 0.5 A 2,000 ms 0.5 A 5,000 ms 0.5 A 10,000 ms Step 5: Re

Page 390

9424200994 Rev N 33 Contact Inputs and Outputs BE1-11g Generator Protection Systems provide up to seven contact inputs, up to eight general-purpose c

Page 391

438 9424200994 Rev N Table 185. Pickup Test Settings (3I0 Mode) Sensing Input Type Range Pickup Setting Time Delay 5 A Low 0.5 A 0 ms Middle 5.0

Page 392

9424200994 Rev N 439 Pickup Verification (I2 Mode) Step 1: Use BESTCOMSPlus to send the operational settings in Table 187 to the BE1-11g. Reset al

Page 393

440 9424200994 Rev N Step 5: Connect a current source to terminals D1 and D2 (A-phase). For a single-phase input test, I2 = Ia / 3. Therefore, the

Page 394

9424200994 Rev N 441 Setting Value BESTCOMSPlus Screen Description Element Mode IG Protection, Current, Instantaneous Overcurrent (50-1) Enables 50-1

Page 395

442 9424200994 Rev N Step 10: (Optional.) Repeat steps 1 through 9 with CT Circuit 2 as the source for protection systems equipped with two sets o

Page 396

9424200994 Rev N 443 Step Time Delay Setting Low Actual Timing High Pass/Fail 4 2,000 ms 1,942 ms 2,058 ms P / F 5 5,000 ms 4,927 ms 5,073 ms P

Page 397

444 9424200994 Rev N Dropout should occur between 93-99% of the actual pickup value. Step Pickup Setting Low Actual Pickup High Low* Actual Dropout

Page 398

9424200994 Rev N 445 Timing Verification (IG Mode) Time Delay Range = 0 to 60,000 ms Timing Accuracy = ±0.5% or ±½ cycle, whichever is greater + 3 cy

Page 399

446 9424200994 Rev N Instantaneous Overcurrent (50) Test BE1-11g

Page 400

9424200994 Rev N 447 Breaker Fail (50BF) Test Functional testing is a way to assess this protection system’s suitability for your application. Functi

Page 401

34 9424200994 Rev N 1. Remove the BE1-11g from service and de-energize it. 2. The contact-sensing input jumpers are located behind the rear termi

Page 402

448 9424200994 Rev N • Fault recording is enabled. • Breaker Status is closed with /IN1. Figure 300. BESTlogicPlus Settings (BFI52 Contact Init

Page 403

9424200994 Rev N 449 Setting Value BESTCOMSPlus Screen Description Element Mode IA Protection, Current, Instantaneous Overcurrent (50-1) Enables 50-1

Page 404

450 9424200994 Rev N Table 195. Control Time Delay Settings Setting Value BESTCOMSPlus Screen Description Phase Pickup 1 A Protection, Current, Bre

Page 405

9424200994 Rev N 451 Inverse Overcurrent (51) Test Functional testing is a way to assess this protection system’s suitability for your application. F

Page 406

452 9424200994 Rev N Figure 302. BESTlogicPlus Settings (Phase Mode) Step 3: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurr

Page 407

9424200994 Rev N 453 Step 2: Prepare to monitor the 51-1 timings. Timing accuracy is verified by measuring the elapsed time between a sensing curren

Page 408

454 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Source CT Circuit 1 Protection, Current, Instantaneous Overcurrent (51-1) Select

Page 409

9424200994 Rev N 455 Timing Verification (3I0 Mode) Step 1: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurrent (51-1) screen an

Page 410

456 9424200994 Rev N Pickup Verification (I2 Mode) Step 1: Use BESTCOMSPlus to send the operational settings in Table 204 to the BE1-11g. Reset

Page 411

9424200994 Rev N 457 for a 1 A BE1-11g with a pickup setting of 0.1, it would require 0.1 times 3 or 0.3 amperes of input current. Step 6: Slowly in

Page 412

9424200994 Rev N 35 3. Locate the two jumper terminal blocks that are mounted on the Digital Circuit Board. The Digital Circuit Board is the middle

Page 413

458 9424200994 Rev N Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3. Step 7: (Optional.) Repeat steps 1 through 6 fo

Page 414

9424200994 Rev N 459 Table 209. Pickup Test Settings (IG Mode) Sensing Input Type Range Pickup Setting Time Dial Time Curve 5 A Low 0.5 A 0 I2 Mid

Page 415

460 9424200994 Rev N Table 211. Timing Test Settings (IG Mode) Sensing Type Time Dial Applied Current 5 A 0.5 1.00 A 2.50 A 12.50 A 5.0 1.00 A 2.50

Page 416

9424200994 Rev N 461 Dropout should occur between 93-99% of the actual pickup value. Step Pickup Setting Low Actual Pickup High Low* Actual Dropout

Page 417

462 9424200994 Rev N Dropout should occur between 93-99% of the actual pickup value. Step Pickup Setting Low Actual Pickup High Low* Actual Dropo

Page 418

9424200994 Rev N 463 Dropout should occur between 93-99% of the actual pickup value. Step Pickup Setting Low Actual Pickup High Low* Actual Dropout H

Page 419

464 9424200994 Rev N Pickup Verification (IG Mode) Pickup Setting Range = 0.5 to 16 A for 5A sensing 0.1 to 3.2 A for 1A sensing 0.01 to 0.8 A

Page 420

9424200994 Rev N 465 4 5.0 I2 0.50 A 1.798 sec 1.988 sec P / F 4 5.0 I2 2.50 A 0.944 sec 1.044 sec P / F 4 9.9 I2 0.20 A 8.300 sec 9.173 s

Page 421

466 9424200994 Rev N Inverse Overcurrent (51) Test BE1-11g

Page 422

9424200994 Rev N 467 Directional Overcurrent (67) Test Functional testing is a way to assess this protection system’s suitability for your applicatio

Page 423

36 9424200994 Rev N Figure 29. Digital Input Conditioning Timing Diagram Setting the Contact Inputs BESTCOMSPlus Navigation Path: Settings Explore

Page 424

468 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Element Mode IA Protection, Current, Instantaneous Overcurrent (50-1) Enables 50

Page 425

9424200994 Rev N 469 zero sequence impedance angles is continuously adjustable between 0 and 90°, the default setting of 80° is used in the test exam

Page 426

470 9424200994 Rev N Table 214. Directional, Negative-Sequence Operational Settings Setting Value BESTCOMSPlus Screen Description Pickup 0 A Protec

Page 427

9424200994 Rev N 471 Table 216. Directional, Negative-Sequence Polarizing, Neutral Operational Settings Setting Value BESTCOMSPlus Screen Description

Page 428

472 9424200994 Rev N sequence line angle. Verify that OUT2 opens at approximately 170 degrees lagging and 350 degrees lagging. OUT2 should remain c

Page 429

9424200994 Rev N 473 Zero-Sequence Current Polarization Use setup commands in Table 212. Using Table 218 as a guide, send the settings to the BE1-11g

Page 430

474 9424200994 Rev N Directional Overcurrent (67) Test BE1-11g

Page 431

9424200994 Rev N 475 Phase Current Differential (87) Test Functional testing is a way to assess this protection system’s suitability for your applica

Page 432

476 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description CT 2 Connection WYE System Parameters, Sensing Transformers Sets the CT 2 connec

Page 433

9424200994 Rev N 477 Setting Value BESTCOMSPlus Screen Description Mode Percent Differential Protection, Current, Phase Differential (87) Sets the ty

Page 434

9424200994 Rev N 37 See Table 6 for a list of settings and their defaults. Table 6. Contact Input Settings Setting Range Increment Unit Default Label

Page 435

478 9424200994 Rev N Figure 307. BESTlogicPlus Settings (87R) Step 8: Slowly decrease the A-phase current in CT circuit 1 or 2 until OUT2 closes

Page 436

9424200994 Rev N 479 Setting Value BESTCOMSPlus Screen Description Nominal Phase Current 5 A System Parameters, Power System Sets the nominal seconda

Page 437

480 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Circuit 1 Tap 2.00 System Parameters, Transformer Setup Sets the tap for circuit

Page 438

9424200994 Rev N 481 Step 5: Slowly increase the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the pickup. This should occur at

Page 439

482 9424200994 Rev N Unrestrained Functional Test Procedure Pickup Verification Step 1: Use BESTCOMSPlus to verify the operational settings in T

Page 440

9424200994 Rev N 483 Second-Harmonic Restraint Verification (Shared) Step 1: Use BESTCOMSPlus to send the operational settings in Table 220 and ve

Page 441

484 9424200994 Rev N Functional Test Reports Restrained Pickup Verification (Maximum Restraint) Pickup Accuracy = ±2% or ±0.05A, whichever is great

Page 442

9424200994 Rev N 485 2nd Harmonic Restraint Verification (Independent) Pickup Accuracy = ±2% or ±0.05A, whichever is greater. Step Pickup Setting Low

Page 443

486 9424200994 Rev N Phase Current Differential (87) Test BE1-11g

Page 444

9424200994 Rev N 487 Neutral Current Differential (87N) Test Functional testing is a way to assess this protection system’s suitability for your appl

Page 445

9424200994 Rev N iii Contents Introduction ...

Page 446

38 9424200994 Rev N BESTlogicPlus expressions for OUT1 through OUT8 and OUTA drive contact outputs OUT1 through OUT8 and OUTA. The state of the con

Page 447

488 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Circuit 1 Ground Compensation No System Parameters, Transformer Setup Disables t

Page 448

9424200994 Rev N 489 Step 5: Slowly increase the magnitude of the IG current input until OUT2 closes and record the pickup. This should occur at 5.0

Page 449

490 9424200994 Rev N Neutral Current Differential (87N) Test BE1-11g

Page 450

9424200994 Rev N 491 Power (32) Test Functional testing is a way to assess this protection system’s suitability for your application. Functional test

Page 451

492 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description 32-1 A Over Enabled Target Configuration, Targets Enables phase A over target fo

Page 452

9424200994 Rev N 493 Step 8: (Optional.) Repeat Steps 1 through 7 for settings group 1, 2, and 3. Step 9: (Optional.) Repeat Steps 1 through 8

Page 453

494 9424200994 Rev N Step 4: With the BE1-11g picked up (OUT2 closed), change the angle of the applied current to lag the voltage by 180 degrees

Page 454

9424200994 Rev N 495 Step Pickup Setting Low Actual Pickup High Low* Actual Dropout High* Pass/Fail 3 500 W 485 W 515 W 475 W 495 W P / F 5 1,0

Page 455

496 9424200994 Rev N Power (32) Test BE1-11g

Page 456

9424200994 Rev N 497 Loss of Excitation - Reverse Var Based (40Q) Test Functional testing is a way to assess this protection system’s suitability for

Page 457

9424200994 Rev N 39 Programmable Hold Timer—Hold Attribute Historically, electromechanical relays have provided trip contact seal-in circuits. These

Page 458

498 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure 311. • Blocking is disabled. •

Page 459

9424200994 Rev N 499 Step 2: Prepare to monitor the 40Q timings. Timing accuracy is verified by measuring the elapsed time between a sensing current

Page 460

500 9424200994 Rev N Loss of Excitation - Reverse Var Based (40Q) Test BE1-11g

Page 461

9424200994 Rev N 501 Distance (21) Test Functional testing is a way to assess this protection system’s suitability for your application. Functional t

Page 462

502 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 312. • Blocking is disabled. •

Page 463

9424200994 Rev N 503 Step 4: Gradually decrease the magnitude all three phase voltages until OUT2 closes. Record the time to trip (OUT1 closes). Ver

Page 464

504 9424200994 Rev N Distance (21) Test BE1-11g

Page 465

9424200994 Rev N 505 Loss of Excitation – Impedance Based (40Z) Test Functional testing is a way to assess this protection system’s suitability for y

Page 466

506 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Phase VT Ratio 1 System Parameters, Sensing Transformers Sets phase VT ratio to

Page 467

9424200994 Rev N 507 opens. Reset the target. Impedance values for this test have been converted to measureable phase-neutral voltages. Figure 313.

Page 468

40 9424200994 Rev N Figure 34. Contact Outputs Screen Contact Output Logic Override Control BESTCOMSPlus Navigation Path: Metering Explorer, Contr

Page 469

508 9424200994 Rev N Step Pickup Setting Low Actual Pickup High Pass/Fail 5 10.0 V (5 Ω) 9.70 V 10.3 V P / F 6 8.00 V 7.92 V 8.08 V P / F

Page 470

9424200994 Rev N 509 Out of Step (78OOS) Test Functional testing is a way to assess this protection system’s suitability for your application. Functi

Page 471

510 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Element Mode Enabled Protection, Impedance, Out of Step (78OOS) Enables the 78O

Page 472

9424200994 Rev N 511 Figure 314. BESTlogicPlus Settings Step 9: Slowly decrease the angles of the voltage inputs to close OUT4 and OUT5 (impedance

Page 473

512 9424200994 Rev N Step 7: Set the voltage input angles to A∠180°, B∠60°, C∠300°. Increase the voltage until OUT3 reopens and record the time be

Page 474

9424200994 Rev N 513 Synchronizer (25A) Test Functional testing is a way to assess this protection system’s suitability for your application. Functio

Page 475

514 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Element Mode PLL Control, Synchronizer (25A) Enables 25A function for PLL opera

Page 476

9424200994 Rev N 515 ` Figure 315. BESTlogicPlus Settings 1 (25A) Step 4: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE

Page 477

516 9424200994 Rev N voltage of 69.28 Vpn, ∠0°, to terminals C17 (Vx-phase) and C18 (Vx-neutral). The 25A Slip Diff digital point should be true. S

Page 478

9424200994 Rev N 517 Frequency Raise/Lower Continuous Output Verification Step 1: Use BESTCOMSPlus to monitor the status of OUT2 (Lower) and OUT3

Page 479

9424200994 Rev N 41 In the Action column, select Pulse from the drop-down menu and click on the green arrow to the right. Pulse override control can

Page 480

518 9424200994 Rev N Figure 316. BESTlogicPlus Settings 2 (25A) Functional Test Report - PLL ΔV Accuracy = ±2% or ±1V, whichever is greater. Slip

Page 481

9424200994 Rev N 519 Anticipatory Functional Test Procedure Voltage Difference Test (ΔV) Step 1: Use BESTCOMSPlus to send the operational setting

Page 482

520 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Volt Pulse Interval (s) 10.0 Control, Synchronizer (25A) Sets the maximum correc

Page 483

9424200994 Rev N 521 Step 8: Slowly decrease the line voltage until the 25A Volt Diff digital point turns off. This should happen at 58.89 V ±1 V.

Page 484

522 9424200994 Rev N Step 3: Increase the phase voltage source until OUT4 begins pulsing. This should occur immediately but reaches the maximum

Page 485

9424200994 Rev N 523 Functional Test Report - Anticipatory ΔV Accuracy = ±2% or ±1 V, whichever is greater. Slip Freq Accuracy = ±0.01 Hz Breaker Clo

Page 486

524 9424200994 Rev N Transformers Aux VT Connection AN System Parameters, Sensing Transformers Sets auxiliary VT connection to AN. Nominal Phase Vo

Page 487

9424200994 Rev N 525 Figure 318. BESTCOMSPlus Synchronizer Screen, 25A Voltage Monitor Logic Step 4: Prepare to monitor the 25VM function operati

Page 488

526 9424200994 Rev N Output Test (25A Voltage Monitor) Step 1: With no voltage applied to either the Line or Auxiliary voltage sources, OUT7 sho

Page 489

9424200994 Rev N 527 Virtual Control Switches (43) Test Functional testing is a way to assess this protection system’s suitability for your applicati

Page 490

42 9424200994 Rev N Contact Inputs and Outputs BE1-11g

Page 491

528 9424200994 Rev N Figure 319. BESTlogicPlus Settings Step 4: Use the Metering Explorer of BESTCOMSPlus to open the Control, Virtual Switches

Page 492

9424200994 Rev N 529 Step 3: Use the Metering Explorer of BESTCOMSPlus to open the Control, Virtual Switches tree branch (Figure 320). Using selec

Page 493

530 9424200994 Rev N Virtual Control Switches (43) Test BE1-11g

Page 494

9424200994 Rev N 531 Logic Timers (62) Test Functional testing is a way to assess this protection system’s suitability for your application. Function

Page 495

532 9424200994 Rev N Figure 321. BESTlogicPlus Settings Step 3: Steps 4 through 6 will initiate the 62-1 timer by changing the 43-1 switch stat

Page 496

9424200994 Rev N 533 Figure 323. Pickup/Dropout Mode Step 10: (Optional.) Repeat steps 1 through 9 for 62-1, 62-2, 62-3, 62-4, 62-5, 62-6, 62-7, an

Page 497

534 9424200994 Rev N despite a second 43-1 OFF to ON initiate signal while the duration timer was active. Figure 324 illustrates the timing relatio

Page 498

9424200994 Rev N 535 Note The 43-1 switch action is performed three times in this test. To illustrate the action of the timer mode, step 4 should be

Page 499

536 9424200994 Rev N Note The 43-1 switch action is performed three times in this test. Follow the timing sequence to illustrate timer mode action.

Page 500

9424200994 Rev N 537 Figure 326. Integrating Timer Mode Latched Mode Step 1: Use BESTCOMSPlus to send the operational settings in Table 245 to th

Page 501

9424200994 Rev N 43 Overexcitation (24) Protection The overexcitation (24) element monitors the volts per hertz ratio and protects transformers and g

Page 502

538 9424200994 Rev N Figure 327. BESTlogicPlus Settings (Latched Mode) Note The 43-1 switch action is performed twice in this test. The 43-2 swit

Page 503

9424200994 Rev N 539 Figure 328. Latched Mode Functional Test Report Function Pass/Fail Pickup/Dropout Mode P / F One-Shot Non-Retriggerable Mod

Page 504

540 9424200994 Rev N Logic Timers (62) Test BE1-11g

Page 505

9424200994 Rev N 541 Lockout Functions (86) Test Functional testing is a way to assess this protection system’s suitability for your application. Fun

Page 506

542 9424200994 Rev N Step 5: Apply voltage to IN1. Verify that OUT1 closes and remains closed. Step 6: Power down the BE1-11g and verify that

Page 507

9424200994 Rev N 543 Breaker Control Switch (101) Test Functional testing is a way to assess this protection system’s suitability for your applicatio

Page 508

544 9424200994 Rev N Figure 330. BESTlogicPlus Settings Step 5: Place the 101 in the CLOSE position by using the Metering Explorer in BESTCOMSP

Page 509

9424200994 Rev N 545 Frequently Asked Questions (FAQ) Electrical/Connections Is the power supply polarity sensitive? No, the power supply will accept

Page 510

546 9424200994 Rev N How can I check the version number of my BE1-11g? The application version can be found in four different ways: One, on the Set

Page 511

9424200994 Rev N 547 Troubleshooting Basler microprocessor-based protection systems are similar in nature to a panel of electromechanical or solid-st

Page 512

44 9424200994 Rev N Trip and Reset Equations Equation 3 and Equation 4 represent the trip time and reset time for a constant V/Hz level. Normally,

Page 513

548 9424200994 Rev N withdrawn and any unsaved changes are lost. When activity at a port is no longer required, access should be terminated. Obtain

Page 514

9424200994 Rev N 549 Why don't the targets or trip LED work properly? If a protective element is tripping at the desired level, but the targets

Page 515

550 9424200994 Rev N Troubleshooting BE1-11g

Page 516

9424200994 Rev N 551 Specifications BE1-11g protection systems used in 50/60 Hz systems have the following features and capabilities. For 25 Hz opera

Page 517

552 9424200994 Rev N Reactive Power 5 Ampere CT Range ... –7,500 var to +7,500 var 1 Ampere CT Range

Page 518

9424200994 Rev N 553 Alarm Pickup Setting Range ... 0.5 to 6 V/Hz Accuracy...

Page 519

554 9424200994 Rev N Voltage Controller Volt Pulse Width Setting Range ... 0.1 to 5 seconds

Page 520

9424200994 Rev N 555 27X - Auxiliary Undervoltage Protection Pickup Setting Range ... 1 to 15

Page 521

556 9424200994 Rev N Directional Supervision Angle (Blinder Angle) Setting Range ... –90 to

Page 522

9424200994 Rev N 557 49RTD - Resistance Temperature Device Protection (Optional) Pickup Setting Range ...

Page 523

9424200994 Rev N 45 Programmable Alarm A 24 Volts per Hz alarm occurs during overexcitation so that corrective action can be taken before the 24 func

Page 524

558 9424200994 Rev N Time Delay & Control Time Setting Range ... 50 to 999 ms Accuracy.

Page 525

9424200994 Rev N 559 59X - Auxiliary Overvoltage Protection Pickup Setting Range ... 1 to 150

Page 526

560 9424200994 Rev N Blinder Angle Setting Range ... 1 to 90 degrees Accuracy...

Page 527

9424200994 Rev N 561 * Recognition time = 2 cycles for 0.57 > pickup, 4 cycles for 0.24 > pickup, 8 cycles for 0.08 > pickup, 16 cycles at p

Page 528

562 9424200994 Rev N Time Delay Setting Range ... 0 to 60,000 ms Accuracy...

Page 529

9424200994 Rev N 563 Terminals (CT1) IA1 ... D1, D2 IB1 ...

Page 530

564 9424200994 Rev N Output Contacts Make and Carry for Tripping Duty ... 30 A for 0.2 seconds per IEEE Std C37.90-2005 -

Page 531

9424200994 Rev N 565 Recognition Time Programmable ... 4 to 255 ms Note All timing specifica

Page 532

566 9424200994 Rev N Note Failure to replace the battery with Basler Electric P/N 38526 may void the warranty. Communication Ports Communication po

Page 533

9424200994 Rev N 567 Standards IEC Standards IEC 60068-1: Environmental Testing Part 1: General and Guidance. Temperature Test IEC 60068-2-1: Basic

Page 534

46 9424200994 Rev N Figure 37. Overexcitation Settings Screen Table 10. Operational Settings Setting Range Increment Unit of Measure Default Mode

Page 535

568 9424200994 Rev N Standards used for evaluation: • UL 508 • ISA 12.12.01 • CSA C22.2 No. 213-M1987 Warning! - EXPLOSION HAZARD Do not discon

Page 536

9424200994 Rev N 569 Specifications - 25 Hz Operation BE1-11g protection systems used in 25 Hz systems have the following features and capabilities.

Page 537

570 9424200994 Rev N Reactive Power 5 Ampere CT Range ... –7,500 var to +7,500 var 1 Ampere CT Range

Page 538

9424200994 Rev N 571 Alarm Pickup Setting Range ... 0.5 to 6 V/Hz Accuracy...

Page 539

572 9424200994 Rev N Voltage Controller Volt Pulse Width Setting Range ... 0.1 to 5 seconds

Page 540

9424200994 Rev N 573 27X - Auxiliary Undervoltage Protection Pickup Setting Range ... 1 to 15

Page 541

574 9424200994 Rev N Directional Supervision Angle (Blinder Angle) Setting Range ... –90 to

Page 542

9424200994 Rev N 575 49RTD - Resistance Temperature Device Protection (Optional) Pickup Setting Range ...

Page 543

576 9424200994 Rev N Time Delay & Control Time Setting Range ... 50 to 999 ms Accuracy.

Page 544

9424200994 Rev N 577 59X - Auxiliary Overvoltage Protection Pickup Setting Range ... 1 to 150

Page 545

9424200994 Rev N 47 Figure 38. Time Shown on Vertical Axis Figure 39. Time Shown on Horizontal Axis Volt/Hz Characteristic1.010.0100.01000.0100%

Page 546

578 9424200994 Rev N Blinder Angle Setting Range ... 1 to 90 degrees Accuracy...

Page 547

9424200994 Rev N 579 * Recognition time = 2 cycles for 0.57 > pickup, 4 cycles for 0.24 > pickup, 8 cycles for 0.08 > pickup, 16 cycles at p

Page 548

580 9424200994 Rev N Time Delay Setting Range ... 0 to 60,000 ms Accuracy...

Page 549

9424200994 Rev N 581 Time Curve Characteristics This chapter provides time curve information for the inverse overcurrent (51), under/overvoltage (27/

Page 550

582 9424200994 Rev N Curve Selection Curve Name Trip Characteristic Constants Reset ∗ A B C N K R I1 CO Inverse Time 8.9341 0.17966 1 2.0938 0.028

Page 551

9424200994 Rev N 583 Table 252. Characteristic Curve Cross-Reference Curve Curve Name Similar To S1 CO Short Inverse ABB CO-2 S2 IAC Short Inverse GE

Page 552

584 9424200994 Rev N Basler Electric protection systems have a maximum time dial setting of 9.9. The Basler Electric equivalent time dial setting f

Page 553

9424200994 Rev N 585 The K factor gives the time that a generator can withstand 1 per unit negative sequence current. For example, with a K factor of

Page 554

586 9424200994 Rev N Figure 334. Time Characteristic Curve S1, Short Inverse (Similar to ABB CO-2) Time Curve Characteristics BE1-11g

Page 555

9424200994 Rev N 587 Figure 335. Time Characteristic Curve S2, Short Inverse (Similar To GE IAC-55) BE1-11g Time Curve Characteristics

Page 556

iv 9424200994 Rev N Frequency (81) Protection ...

Page 557

48 9424200994 Rev N Assuming a Vnom of 69.3 Vpn, 1 pu volts/hertz = (69.3 * √3) / 60 = 2.00. Using IEEE Std C37.102-2006 - IEEE Guide for AC Genera

Page 558

588 9424200994 Rev N Figure 336. Time Characteristic Curve A, Standard Inverse (BS 142) Time Curve Characteristics BE1-11g

Page 559

9424200994 Rev N 589 Figure 337. Time Characteristic Curve A1, Inverse (IEC 60255-151 Ed. 1) BE1-11g Time Curve Characteristics

Page 560

590 9424200994 Rev N Figure 338. Time Characteristic Curve I1, Inverse Time (Similar to ABB CO-8) Time Curve Characteristics BE1-11g

Page 561

9424200994 Rev N 591 Figure 339. Time Characteristic Curve I2, Inverse Time (Similar to GE IAC-51) BE1-11g Time Curve Characteristics

Page 562

592 9424200994 Rev N Figure 340. Time Characteristic Curve M, Moderately Inverse (Similar to ABB CO-7) Time Curve Characteristics BE1-11g

Page 563

9424200994 Rev N 593 Figure 341. Time Characteristic Curve D1, Moderately Inverse (IEC 60255-151 Ed. 1) 0.010.101.0010.00100.001000.001 10 100MUL

Page 564

594 9424200994 Rev N Figure 342. Time Characteristic Curve L1, Long Inverse (Similar to ABB CO-5) Time Curve Characteristics BE1-11g

Page 565

9424200994 Rev N 595 Figure 343. Time Characteristic Curve L2, Long Inverse (Similar To GE IAC-66) BE1-11g Time Curve Characteristics

Page 566

596 9424200994 Rev N Figure 344. Time Characteristic Curve G, Long Time Inverse (BS 142) Time Curve Characteristics BE1-11g

Page 567

9424200994 Rev N 597 Figure 345. Time Characteristic Curve V1, Very Inverse (Similar to ABB CO-9) BE1-11g Time Curve Characteristics

Page 568

9424200994 Rev N 49 Sync-Check (25) Protection The sync-check (25) element provides breaker closing supervision by comparing the voltage magnitude, a

Page 569

598 9424200994 Rev N Figure 346. Time Characteristic Curve V2, Very Inverse (Similar to GE IAC-53) Time Curve Characteristics BE1-11g

Page 570

9424200994 Rev N 599 Figure 347. Time Characteristic Curve B, Very Inverse (BS 142) BE1-11g Time Curve Characteristics

Page 571

600 9424200994 Rev N Figure 348. Time Characteristic Curve B1, Very Inverse (IEC 60255-151 Ed. 1) Time Curve Characteristics BE1-11g

Page 572

9424200994 Rev N 601 Figure 349. Time Characteristic Curve E3, Very Inverse (IEC 60255-151 Ed. 1) 0.010.101.0010.00100.001000.001 10 100MULTIPLES

Page 573

602 9424200994 Rev N Figure 350. Time Characteristic Curve E1, Extremely Inverse (Similar to ABB CO-11) Time Curve Characteristics BE1-11g

Page 574

9424200994 Rev N 603 Figure 351. Time Characteristic Curve E2, Extremely Inverse (Similar to GE IAC-77) BE1-11g Time Curve Characteristics

Page 575

604 9424200994 Rev N Figure 352. Time Characteristic Curve C, Extremely Inverse (BS 142) Time Curve Characteristics BE1-11g

Page 576

9424200994 Rev N 605 Figure 353. Time Characteristic Curve C1, Extremely Inverse (IEC 60255-151 Ed. 1) BE1-11g Time Curve Characteristics

Page 577

606 9424200994 Rev N Figure 354. Time Characteristic Curve F1, Extremely Inverse (IEC 60255-151 Ed. 1) 0.010.101.0010.00100.001000.001 10 100MU

Page 578

9424200994 Rev N 607 Figure 355. Time Characteristic Curve D, Definite Time (Similar To ABB CO-6) BE1-11g Time Curve Characteristics

Page 579

50 9424200994 Rev N Terminals Va (C13), Vb (C14), and Vc (C15) are connected in parallel. The single-phase signal is connected between the parallel

Page 580

608 9424200994 Rev N Figure 356. 46 Time Characteristic Curve NOTE: Curves are shown as extending farther to the left than they will in practice.

Page 581

9424200994 Rev N 609 Under/Overvoltage (27/59) The 27 and 59 elements have independent user defined definite and inverse time delays. The inverse tim

Page 582

610 9424200994 Rev N Figure 357. Undervoltage (27) Inverse Time Curve 0.101.0010.00100.000 1TIME IN SECONDS MULTIPLES OF PICKUP 9.99876543210.5

Page 583

9424200994 Rev N 611 Overvoltage (59) Inverse Time Curve The overvoltage inverse time curve is defined by Equation 35 and shown in Figure 358. =

Page 584

612 9424200994 Rev N Figure 358. Overvoltage (59) Inverse Time Curve 0.101.0010.00100.001 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2TIME IN SECONDS

Page 585

9424200994 Rev N 613 Overexcitation (24) General The inverse time curves for the overexcitation (24) element are defined below. Equation 36 and Equat

Page 586

614 9424200994 Rev N Figure 359. V/Hz Characteristic (M-1)^0.5 – Time on Vertical Axis Figure 360. V/Hz Characteristic (M-1)^0.5 – Time on Horiz

Page 587

9424200994 Rev N 615 Figure 361. V/Hz Characteristic (M-1)^1 – Time on Vertical Axis Figure 362. V/Hz Characteristic (M-1)^1 – Time on Horizontal

Page 588

616 9424200994 Rev N Figure 363. V/Hz Characteristic (M-1)^2 – Time on Vertical Axis Figure 364. V/Hz Characteristic (M-1)^2 – Time on Horizonta

Page 589

9424200994 Rev N 617 RTD Module The RTD (Resistance Temperature Detector) module is an optional remote device that provides RTD inputs, analog inputs

Page 590

9424200994 Rev N 51 Phase VT Connection Phase Rotation Aux VT Connection Secondary Phase Voltage (Phase-Neutral) Secondary Aux Voltage Angle Compensa

Page 591

618 9424200994 Rev N Mounting RTD modules are contained in a potted plastic case and may be mounted in any convenient position using UNC ¼-20 or eq

Page 592

9424200994 Rev N 619 Connections RTD module connections are dependent on the application. Incorrect wiring may result in damage to the module. Note

Page 593

620 9424200994 Rev N Figure 366. Input and Output Terminals Table 256. Input and Output Terminals Connector Description TB1 Operating Power and Al

Page 594

9424200994 Rev N 621 Figure 367. Analog Inputs - Voltage Input Connections Figure 368. Analog Inputs - Current Input Connections External RTD Input

Page 595

622 9424200994 Rev N Figure 370. External Three-Wire RTD Input Connections RTD Module Communications Setup Procedure Communication between the BE1

Page 596

9424200994 Rev N 623 5. Open the RTD Module plugin in BESTCOMSPlus. 6. Pull down the Communication menu and select New Connection  RTD Module. The

Page 597

624 9424200994 Rev N Figure 372. Procedure 2 Connect to RTD Module 1. Connect an Ethernet cable directly between the PC and RTD module. 2. Apply

Page 598

9424200994 Rev N 625 10. Click Send to Device. A password is required. The default password is “OEM”. Click Close. 11. Click Cancel on the Device Dis

Page 599

626 9424200994 Rev N Figure 373. BESTCOMSPlus Select Language Screen The BESTCOMSPlus splash screen is shown for a brief time. See Figure 374. Fi

Page 600

9424200994 Rev N 627 Figure 376. RTD Module Connection Screen Wait until scanning is complete. See Figure 377. Figure 377. Scanning for Connected D

Page 601

52 9424200994 Rev N If the 60FL element trip logic is true and Block Phase/V1 is enabled, all functions that use the phase voltage are blocked. See

Page 602

628 9424200994 Rev N The Configure - RTD Module screen shown in Figure 379 appears. The BE1-11g uses the Device Address to communicate with the con

Page 603

9424200994 Rev N 629 screen is found by selecting Activate Device from the Tools pull-down menu of the BESTCOMSPlus main screen. Device Info Informat

Page 604

630 9424200994 Rev N Figure 383. Login Screen Enter the Password and then click the Log In button. The default password is “OEM”. The Device Secur

Page 605

9424200994 Rev N 631 Figure 385. Module 1 Input #1 Screen Table 257 summarizes the configuration settings for remote analog inputs. Table 257. Confi

Page 606

632 9424200994 Rev N Figure 386. Module 1 Output #1 Screen Table 258 summarizes the configuration settings for remote analog outputs. Table 258. C

Page 607

9424200994 Rev N 633 Figure 387. RTD Type Selection Screen Use the Settings Explorer to open the Programmable Outputs, Remote RTD, RTD Block Configu

Page 608

634 9424200994 Rev N Maximum Lead Length ... 150 feet (4.25 km) with 22 AWG (0.326 mm2) wire Sensing Current Level ... 2.5

Page 609

9424200994 Rev N 635 IEC 60255-5: Electrical Insulation Tests for Electrical Relays. Dielectric Test and Impulse Test IEC 60255-6: Electrical Relay

Page 610

636 9424200994 Rev N expected to provide long-term operation in a rugged environment. Note that the vibration and temperature extremes listed in th

Page 611

9424200994 Rev N 637 Digital Points The status of all BE1-11g digital points is displayed in the Metering Explorer of BESTCOMSPlus® under Status, Dig

Page 612

9424200994 Rev N 53 Figure 43. Sync-Check Settings Screen Table 13. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabl

Page 613

638 9424200994 Rev N Name Number 27X-3 Pickup 83 27X-3 Trip 84 27X-3 V1 89 27X-3 V2 86 27X-4 3RD 96 27X-4 3V0 93 27X-4 AUX 95 27X-4 Block 90 27X-4

Page 614

9424200994 Rev N 639 Name Number 49RTD-1 RTD 2-7 1043 49RTD-1 RTD 2-8 1044 49RTD-1 RTD 2-9 1045 49RTD-1 Trip 1024 49RTD-10 Block 1884 49RTD-10 Pickup

Page 615

640 9424200994 Rev N Name Number 49RTD-14 RTD 1-6 2000 49RTD-14 RTD 1-7 2001 49RTD-14 RTD 1-8 2002 49RTD-14 RTD 1-9 2003 49RTD-14 RTD 2-1 2007 49RT

Page 616

9424200994 Rev N 641 Name Number 49RTD-5 RTD 2-8 1152 49RTD-5 RTD 2-9 1153 49RTD-5 Trip 1132 49RTD-6 Block 1157 49RTD-6 Pickup 1158 49RTD-6 RTD 1-1 1

Page 617

642 9424200994 Rev N Name Number 50-1 C 171 50-1 IND GND 174 50-1 Neg SEQ 172 50-1 Pickup 167 50-1 Pos SEQ 181 50-1 Prevent Config Option Change 18

Page 618

9424200994 Rev N 643 Name Number 51-1 67T IND GND 300 51-1 67T Neg SEQ 298 51-1 67T Pos SEQ 302 51-1 67T Residual 299 51-1 A 289 51-1 B 290 51-1 Bloc

Page 619

644 9424200994 Rev N Name Number 51-7 67T Pos SEQ 422 51-7 67T Residual 419 51-7 A 409 51-7 B 410 51-7 Block 406 51-7 C 411 51-7 IND GND 414 51-7 N

Page 620

9424200994 Rev N 645 Name Number 62-7 616 62-7 Block 614 62-7 Initiate 615 62-8 619 62-8 Block 617 62-8 Initiate 618 67 NEG SEQ DIR F 157 67 NEG SEQ

Page 621

646 9424200994 Rev N Name Number Analog Input Protection 4 Pickup 984 Analog Input Protection 4 Trip 985 Analog Input Protection 5 990 Analog Input

Page 622

9424200994 Rev N 647 Name Number GGIO-CTL1 Oper01Alarm 1569 GGIO-CTL1 Oper01Default 1568 GGIO-CTL1 Oper02 1570 GGIO-CTL1 Oper02Alarm 1572 GGIO-CTL1 O

Page 623

54 9424200994 Rev N Sync-Check (25) Protection BE1-11g

Page 624

648 9424200994 Rev N Name Number GGIO-CTL3 Oper10 1690 GGIO-CTL3 Oper10Alarm 1692 GGIO-CTL3 Oper10Default 1691 GGIO-CTL3 Oper11 1693 GGIO-CTL3 Oper

Page 625

9424200994 Rev N 649 Name Number INDGGIO4_IND06 1303 INDGGIO4_IND07 1304 INDGGIO4_IND08 1305 INDGGIO4_IND09 1306 INDGGIO4_IND10 1307 INDGGIO4_IND11 1

Page 626

650 9424200994 Rev N Name Number Programmable Alarm 7 755 Programmable Alarm 8 756 Programmable Alarm 9 757 Real Time Clock 730 Relay Alarms 793 Re

Page 627

9424200994 Rev N 651 Revision History Table 260 provides a historical summary of the changes made to the BE1-11g hardware. Application firmware chang

Page 628

652 9424200994 Rev N Table 261. Application Firmware Revision History Firmware Version and Date Change 1.01.00, Apr-09 • Initial release 1.02.00,

Page 629

9424200994 Rev N 653 Firmware Version and Date Change 2.07.00, Nov-13 • Made alarms available in BESTlogicPlus • Expanded Target Reset logic point

Page 630

654 9424200994 Rev N Software Version and Date Change 2.05.00, Jul-09 • Updated Basler Electric Device Package Uploader screen • Changed 40Q pick

Page 631

9424200994 Rev N 655 Software Version and Date Change 3.01.01, Nov-12 • Added Delta/Wye Compensation Enable setting on the Distance (21) settings sc

Page 632

656 9424200994 Rev N Manual Revision and Date Change E, Mar-11 • Replaced Figure 3-13, Auto Export Metering (Added Filter button on screen) • Rep

Page 633

9424200994 Rev N 657 Manual Revision and Date Change N, Sep-14 • Added Conformal Coating to Option 2 in Figures 1 and 264 • Added power supply burd

Page 634

9424200994 Rev N 55 Phase Undervoltage (27P) Protection Five phase undervoltage (27P) elements monitor the sensing voltage applied to the BE1-11g. An

Page 635

658 9424200994 Rev N Revision History BE1-11g

Page 637

12570 State Route 143 Highland IL 62249-1074 USA Tel: +1 618.654.2341 Fax: +1 618.654.2351 email: [email protected] P.A.E. Les Pins 67319 Wasselonne

Page 638

56 9424200994 Rev N Trip The Trip output becomes true when an undervoltage pickup condition persists for the duration of the element Time Delay set

Page 639

9424200994 Rev N 57 Operational Settings Phase undervoltage element operational settings are configured on the Undervoltage (27P) settings screen (Fi

Page 640

9424200994 Rev N v Out of Step (78OOS) Protection ...

Page 641

58 9424200994 Rev N Phase Undervoltage (27P) Protection BE1-11g

Page 642

9424200994 Rev N 59 Auxiliary Undervoltage (27X) Protection Four auxiliary undervoltage (27X) elements monitor the phase and auxiliary voltage applie

Page 643

60 9424200994 Rev N parameter set to AB, for example, will display the metering data as AB in fault records and display the pickup setting as Vpp i

Page 644

9424200994 Rev N 61 Element Blocking Fuse Loss The fuse loss (60FL) element of the BE1-11g can be used to block 27X protection when fuse loss or loss

Page 645

62 9424200994 Rev N Figure 47. Auxiliary Undervoltage Settings Screen Table 18. Operational Settings Setting Range Increment Unit of Measure Defau

Page 646

9424200994 Rev N 63 Negative-Sequence Voltage (47) Protection Negative-sequence voltage protection is included as a mode of the 27X (Auxiliary Underv

Page 647

64 9424200994 Rev N Negative-Sequence Voltage (47) Protection BE1-11g

Page 648

9424200994 Rev N 65 Phase Overvoltage (59P) Protection Four phase overvoltage (59P) elements monitor the sensing voltage applied to the BE1-11g. An e

Page 649

66 9424200994 Rev N Trip The Trip output becomes true if an overvoltage pickup condition persists for the duration of the element Time Delay settin

Page 650

9424200994 Rev N 67 Figure 49. Overvoltage Settings Screen Table 20. Operational Settings Setting Range Increment Unit of Measure Default Mode Disab

Page 651

vi 9424200994 Rev N Alarms ...

Page 652

68 9424200994 Rev N Phase Overvoltage (59P) Protection BE1-11g

Page 653

9424200994 Rev N 69 Auxiliary Overvoltage (59X) Protection Four auxiliary overvoltage (59X) elements monitor the phase and auxiliary voltage applied

Page 654

70 9424200994 Rev N pickup setting as Vpp in BESTCOMSPlus. See Table 21 for a full list of possible settings. The Aux VT Connection parameter is fo

Page 655

9424200994 Rev N 71 element Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the Elements view, the def

Page 656

72 9424200994 Rev N Table 23. Operational Settings Setting Range Increment Unit of Measure Default Mode* Disabled, 3V0, V1, V2, Vx Fundamental, Vx

Page 657

9424200994 Rev N 73 Stator Ground (64G) Protection The BE1-11g provides ground protection for 100% of the stator winding on high-impedance, grounded

Page 658

74 9424200994 Rev N Stator Ground (64G) Protection BE1-11g

Page 659

9424200994 Rev N 75 Vector Jump (78V) Protection The vector jump (78V) element protects the generator by disconnecting it from the grid when a loss o

Page 660

76 9424200994 Rev N If the 60FL element trip logic is true and Block Phase/V1 is enabled, all functions that use the phase voltage are blocked. See

Page 661

9424200994 Rev N 77 Table 25. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabled or Enabled n/a n/a Disabled Source P

Page 662

9424200994 Rev N vii Settings File Management ...

Page 663

78 9424200994 Rev N Vector Jump (78V) Protection BE1-11g

Page 664

9424200994 Rev N 79 Frequency (81) Protection Eight frequency (81) elements monitor the frequency of the sensing voltage applied to the BE1-11g. An e

Page 665

80 9424200994 Rev N Pickup and Trip The Pickup output occurs first, followed by the Trip output. Pickup The Pickup output becomes true when the mea

Page 666

9424200994 Rev N 81 Sensing Source Frequency ROC protection can be applied to the voltage sensed at the BE1-11g phase VT input or auxiliary VT (Vx) i

Page 667

82 9424200994 Rev N Logic Connections Frequency element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus. The frequency eleme

Page 668

9424200994 Rev N 83 Setting Range Increment Unit of Measure Default Voltage Inhibit 0 or 15 to 250 0.1 volts* 20 81ROC Over Frequency Inhibit 15 to 7

Page 669

84 9424200994 Rev N Frequency (81) Protection BE1-11g

Page 670

9424200994 Rev N 85 Negative-Sequence Overcurrent (46) Protection Negative-sequence overcurrent protection is included as a mode of the 50 (Instantan

Page 671

86 9424200994 Rev N Figure 57. Sequence Components for an A-B Fault Coordination Settings The 51-x negative-sequence settings should be checked fo

Page 672

9424200994 Rev N 87 Instantaneous Overcurrent (50) Protection Six instantaneous overcurrent (50) elements monitor the current applied to the BE1-11g.

Commentaires sur ces manuels

Pas de commentaire