INSTRUCTION MANUAL FOR OVERCURRENT RELAY BE1-50/51B-232 Publication: 9252000896 Revision: B 12/08
ii BE1-50/51B-232 General Information 9252000896 Rev B This page intentionally left blank.
9252000896 Rev B BE1-50/51B-232 General Information 1-1 SECTION 1 GENERAL INFORMATION INTRODUCTION BE1-50/51B-232 protective relays are direct rep
Advantages BE1-50/51B-232 overcurrent relays have many advantages over other overcurrent relays. The primary advantages are: Time characteristics a
9252000896 Rev B BE1-50/51B-232 General Information 1-3 Time characteristic curve constants are listed in Tables 1-2 and 1-3. Constants have been se
Integrating reset characteristics are defined by the following equation and shown in Figure 1-1. Equation constants are provided in Tables 1-2 or 1-3.
both SW3-1 and SW3-2 provides an additional delay of 0.3 second. Section 2 illustrates the location of SW3. The instantaneous element in BE1-50/51B-23
P0048-11 Figure 1-3. Burden Characteristics Frequency Response A change of ±5 Hz from the nominal 60 Hz current causes <0.5% change in the current
Figure 1-4. Harmonic Rejection Target Indicators Gravity latched, manually reset targets indicate that current of 0.2 amperes or greater was present
1-8 BE1-50/51B-232 General Information 9252000896 Rev B Vibration Withstands 2 G in each of three mutually perpendicular planes swept over the range
9252000896 Rev B BE1-50/51B-232 Controls and Indicators i SECTION 2 CONTROLS AND INDICATORS TABLE OF CONTENTS SECTION 2 CONTROLS AND INDICATORS
ii BE1-50/51B-232 Controls and Indicators 9252000896 Rev B This page intentionally left blank.
SECTION 2 CONTROLS AND INDICATORS INTRODUCTION Figure 2-1 illustrates the front panel controls and indicators of the BE1-50/51B-232. Figure 2-2 illu
P0053-50SW3 Figure 2-2. Location of SW3 2-2 BE1-50/51B-232 Controls and Indicators 9252000896 Rev B
9252000896 Rev B BE1-50/51B-232 Controls and Indicators 2-3 Table 2-1. BE1-50/51B-232 Controls and Indicators (Refer to Figures 2-1 and 2-2) Locator
2-4 BE1-50/51B-232 Controls and Indicators 9252000896 Rev B This page intentionally left blank.
9252000896 Rev B BE1-50/51B-232 Functional Description i SECTION 3 FUNCTIONAL DESCRIPTION TABLE OF CONTENTS SECTION 3 FUNCTIONAL DESCRIPTION ..
ii BE1-50/51B-232 Functional Description 9252000896 Rev B This page intentionally left blank.
9252000896 Rev B BE1-50/51B-232 Functional Description 3-1 SECTION 3 FUNCTIONAL DESCRIPTION GENERAL BE1-50/51B-232 Overcurrent Relays are micropro
Outputs Instantaneous and Timed System circuit breakers controlled by the output contacts can be manually tripped by applying a short across the TIME
9252000896 Rev B BE1-50/51B-232 Installation i SECTION 4 INSTALLATION TABLE OF CONTENTS SECTION 4 INSTALLATION ...
INTRODUCTION This instruction manual provides information about the operation and installation of the BE1-50/51B-232 Overcurrent Relay. To accomplish
ii BE1-50/51B-232 Installation 9252000896 Rev B This page intentionally left blank.
SECTION 4 INSTALLATION GENERAL When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to prevent damage
Figure 4-2. Panel Drilling Diagram for S1 Case, Semi-Flush Mounting 4-2 BE1-50/51B-232 Installation 9252000896 Rev B
Figure 4-3. Panel Drilling Diagram for S1 Case, Projection Mounting 9252000896 Rev B BE1-50/51B-232 Installation 4-3
4.034.03.31.756.19(19.1)(7.9)(102.4)(102.4)(157.2)10-32 SCREWS MOUNTING PANEL.25(6.4)AA5/16-18 STUD2 PLACESTERMINAL EXTENSION (TYP.)FOR DETAILE
curve E (extremely inverse) selected (SW3-3 set to OFF) and the TIME DIAL set to 2.0. The feeder reclosing relay is set for two reclose attempts at 3
Equation for time to trip during rewind (before relay is reset). Rewind FullTime RewindTrip FullTOccurence This Trip Second Operation 15.530
Figure 4-7. DC Control Connections MAINTENANCE BE1-50/51B-232 overcurrent relays require no preventive maintenance. However, periodic checks should
4-8 BE1-50/51B-232 Installation 9252000896 Rev B This page intentionally left blank.
9252000896 Rev B BE1-50/51B-232 Testing i SECTION 5 TESTING TABLE OF CONTENTS SECTION 5 TESTING ...
First Printing: January 2007 Printed in USA © 2008 Basler Electric, Highland Illinois 62249 USA All Rights Reserved December 2008 CONFIDENTIAL
ii BE1-50/51B-232 Testing 9252000896 Rev B This page intentionally left blank.
SECTION 5 TESTING GENERAL Dielectric testing, operational testing, and periodic testing are described in the following paragraphs. DIELECTRIC TEST I
Figure 5-1. Pickup and Timing Test Setup Figure 5-2. Target Operational Test Setup 5-2 BE1-50/51B-232 Testing 9252000896 Rev B
NOTE When testing TIME overcurrent functions, INST PICKUP settings of 00 will affect the calibration of the TIME functions. TIME PICKUP settings of 00
Time Dial Test Perform preliminary setup: Connect test setup as shown in Figure 5-1. Insure that SW3 switches are set: SW3-1 to OFF, SW3-2 to OF
9252000896 Rev B BE1-50/51B-232 Testing 5-5 Step 4. Connect a jumper between INST MANUAL TRIP test points. Check that INST target operates. Step 5.
5-6 BE1-50/51B-232 Testing 9252000896 Rev B This page intentionally left blank.
9252000896 Rev B BE1-50/51B-232 Time Characteristic Curves i APPENDIX A TIME CHARACTERISTIC CURVES TABLE OF CONTENTS APPENDIX A TIME CHARACTERI
ii BE1-50/51B-232 Time Characteristic Curves 9252000896 Rev B This page intentionally left blank.
APPENDIX A TIME CHARACTERISTIC CURVES TIME CHARACTERISTIC CURVES Figures A-1 through A-14 illustrate the time characteristic curves that are program
9252000896 Rev B BE1-50/51B-232 Introduction iii REVISION HISTORY The following information provides a historical summary of the changes made to th
Figure A-2. Time Characteristic Curve, L-Long Inverse (SW3-3 OFF, Similar to ABB CO-5) A-2 BE1-50/51B-232 Time Characteristic Curves 9252000896 Rev
Figure A-3. Time Characteristic Curve, D-Definite Time (Similar to ABB CO-6) 9252000896 Rev B BE1-50/51B-232 Time Characteristic Curves A-3
Figure A-4. Time Characteristic Curve, M-Moderately Inverse (Similar to ABB CO-7) A-4 BE1-50/51B-232 Time Characteristic Curves 9252000896 Rev B
Figure A-5. Time Characteristic Curve, I-Inverse (SW3-3 OFF, Similar to ABB CO-8) 9252000896 Rev B BE1-50/51B-232 Time Characteristic Curves A-5
Figure A-6. Time Characteristic Curve, V-Very Inverse (SW3-3 OFF, Similar to ABB CO-9) A-6 BE1-50/51B-232 Time Characteristic Curves 9252000896 Re
Figure A-7. Time Characteristic Curve, E-Extremely Inverse (SW3-3 OFF, Similar to ABB CO-11) 9252000896 Rev B BE1-50/51B-232 Time Characteristic Cur
Figure A-8. Time Characteristic Curve, BS142-B (BS142 Very Inverse) A-8 BE1-50/51B-232 Time Characteristic Curves 9252000896 Rev B
Figure A-9. Time Characteristic Curve, BS142-C (BS142 Extremely Inverse) 9252000896 Rev B BE1-50/51B-232 Time Characteristic Curves A-9
Figure A-10. Time Characteristic Curve, S2-Short Inverse (SW3-3 ON, Similar to GE IAC 55) A-10 BE1-50/51B-232 Time Characteristic Curves 9252000896
Figure A-11. Time Characteristic Curve, L2-Long Inverse (SW3-3 ON, Similar to GE IAC 66) 9252000896 Rev B BE1-50/51B-232 Time Characteristic Curves
iv BE1-50/51B-232 Introduction 9252000896 Rev B This page intentionally left blank.
Figure A-12. Time Characteristic Curve, I2-Inverse (SW3-3 ON, Similar to GE IAC 51) A-12 BE1-50/51B-232 Time Characteristic Curves 9252000896 Rev B
Figure A-13. Time Characteristic Curve, V2-Very Inverse (SW3-3 ON, Similar to GE IAC 53) 9252000896 Rev B BE1-50/51B-232 Time Characteristic Curves
Figure A-14. Time Characteristic Curve, E2-Extremely Inverse (SW3-3 ON, Similar to GE IAC 77) A-14 BE1-50/51B-232 Time Characteristic Curves 925200
ROUTE 143, BOX 269 HIGHLAND, IL 62249 USA http://www.basler.com, [email protected] PHONE +1 618-654-2
9252000896 Rev B BE1-50/51B-232 Introduction v CONTENTS SECTION 1 GENERAL INFORMATION ...
vi BE1-50/51B-232 Introduction 9252000896 Rev B This page intentionally left blank.
9252000896 Rev B BE1-50/51B-232 General Information i SECTION 1 GENERAL INFORMATION TABLE OF CONTENTS SECTION 1 GENERAL INFORMATION ....
Commentaires sur ces manuels